GESINGLEUPS-MIB :: upsBatteryStatusgen

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › GESINGLEUPS-MIB › upsBatteryStatusgen

upsBatteryStatusgen

Module: GESINGLEUPS-MIB

OID (symbolic): GESINGLEUPS-MIB::upsBatteryStatusgen

OID (numeric): 1.3.6.1.4.1.818.1.1.10.2.1

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: The indication of the capacity remaining in the UPS system's batteries. A value of batteryNormal indicates that the remaining run-time is greater than upsConfigLowBattTime. A value of batteryLow indicates that the remaining battery run-time is less than or equal to upsConfigLowBattTime. A value of batteryDepleted indicates that the UPS will be unable to sustain the present load when and if the utility power is lost (including the possibility that the utility power is currently absent and the UPS is unable to sustain the output).(*)

What is upsBatteryStatusgen?

Indicates the overall condition of the UPS battery: unknown, normal, low, or depleted. A value of batteryLow means the remaining run-time has fallen to or below the configured upsConfigLowBattTimegen threshold, while batteryDepleted warns that the UPS could not sustain the current load if utility power were lost right now.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.2.1
snmpwalk -v2c -c public <target> GESINGLEUPS-MIB::upsBatteryStatusgen

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.2.1.1
snmpget -v2c -c public <target> GESINGLEUPS-MIB::upsBatteryStatusgen.1

Start monitoring GE Digital Energy single-unit UPS system with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the GESINGLEUPS-MIB::upsBatteryStatusgen OID value, configure state conditions and alerts, and monitor any GE Digital Energy single-unit UPS system from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.818imvGE-PARALLELUPS
1.3.6.1.4.1.818.1geHardwareGE-PARALLELUPS
1.3.6.1.4.1.818.1.1geUPSGE-PARALLELUPS
1.3.6.1.4.1.818.1.1.10geGenericUPSGE-PARALLELUPS
1.3.6.1.4.1.818.1.1.10.2upsBattery_genGE-PARALLELUPS
Numeric OIDNameModule
1.3.6.1.4.1.818.1.1.10.2.1upsBatteryStatusgenGESINGLEUPS-MIB