All MIBs › GE-PARALLELUPS › upsSecondsOnBattery_gen
upsSecondsOnBattery_gen
Module: GE-PARALLELUPS
OID (symbolic): GE-PARALLELUPS::upsSecondsOnBattery_gen
OID (numeric): 1.3.6.1.4.1.818.1.1.10.2.2
Node type: OBJECT-TYPE
Type: NonNegativeInteger32
Access: read-only
Description: If the unit is on battery power, the elapsed time since the UPS last switched to battery power, or the time since the network management subsystem was last restarted, whichever is less. Zero shall be returned if the unit is not on battery power.(*)
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.2.2 snmpwalk -v2c -c public <target> GE-PARALLELUPS::upsSecondsOnBattery_gen
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.818.1.1.10.2.2.1 snmpget -v2c -c public <target> GE-PARALLELUPS::upsSecondsOnBattery_gen.1
Start monitoring GE parallel-redundant UPS installation with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the GE-PARALLELUPS::upsSecondsOnBattery_gen OID value, configure state conditions and alerts, and monitor any GE parallel-redundant UPS installation from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.818 | imv | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1 | geHardware | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1 | geUPS | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1.10 | geGenericUPS | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1.10.2 | upsBattery_gen | GE-PARALLELUPS |
| 1.3.6.1.4.1.818.1.1.10.2.2 | upsSecondsOnBattery_gen | GE-PARALLELUPS |