xupsEnvRemoteTemp

Module: EATON-EMP-MIB

OID (symbolic): EATON-EMP-MIB::xupsEnvRemoteTemp

OID (numeric): 1.3.6.1.4.1.534.1.6.5

Node type: OBJECT-TYPE

Type: Integer32

Access: read-only

Description: The reading of an EMP's temperature sensor.

What is xupsEnvRemoteTemp?

This is the current temperature reading, in whole degrees Celsius, taken by the Environment Monitoring Probe's built-in temperature sensor. Because the EMP is a probe physically separate from the UPS or gateway it attaches to, this value lets admins monitor ambient conditions in a server room or cabinet independent of the UPS's own internal temperature reading. A reading of 45 approaching the configured xupsEnvRemoteTempUpperLimit would flag that the room is overheating and warrants checking cooling before the temperature alarm trips.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.534.1.6.5
snmpwalk -v2c -c public <target> EATON-EMP-MIB::xupsEnvRemoteTemp

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.534.1.6.5.1
snmpget -v2c -c public <target> EATON-EMP-MIB::xupsEnvRemoteTemp.1

Start monitoring Eaton UPS/power equipment with Environmental Monitoring Probe (EMP) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-EMP-MIB::xupsEnvRemoteTemp OID value, configure state conditions and alerts, and monitor any Eaton UPS/power equipment with Environmental Monitoring Probe (EMP) from a single console.

How to Use in IPNetwork Monitor

Select an Eaton UPS/power equipment with Environmental Monitoring Probe (EMP) as the target host to create a monitor — the SNMP service should be up and running on it. Click New Monitor, then check SNMP Custom on the Favorites tab, click Next, and confirm the host. On the next page, click Select... to open the built-in SNMP MIB Browser and type xupsEnvRemoteTemp into the Find box to locate it in the OID tree, then select it and click OK. The reading of an EMP's temperature sensor. On the monitor's Main parameters page you can set the target's SNMP port (default 161), credentials, polling interval, and other settings — see the SNMP Monitor help for details. On the State conditions and Alerting tabs, configure when the monitor should change state and trigger an alert; since this is an Integer32-type OID, Value bounds is the most useful condition here — trigger an alert if the reported value exceeds the level expected for healthy operation, since sustained high temperature often precedes thermal shutdown or hardware degradation. Click Finish to create the monitor; you can adjust any parameter later.

OID Breakdown

Upper-level ancestors (9 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.534eatonEATON-OIDS
1.3.6.1.4.1.534.1xupsMIBEATON-OIDS
1.3.6.1.4.1.534.1.6xupsEnvironmentEATON-OIDS
Numeric OIDNameModule
1.3.6.1.4.1.534.1.6.5xupsEnvRemoteTempEATON-EMP-MIB