EATON-EMP-MIB :: xupsEnvRemoteHumidityUpperLimit

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsEATON-EMP-MIBxupsEnvRemoteHumidityUpperLimit

xupsEnvRemoteHumidityUpperLimit

Module: EATON-EMP-MIB

OID (symbolic): EATON-EMP-MIB::xupsEnvRemoteHumidityUpperLimit

OID (numeric): 1.3.6.1.4.1.534.1.6.12

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: The Upper Limit of the EMP humidity reading; if xupsEnvRemoteHumidity rises above this value, the xupsRemoteHumidityBad alarm will occur. This value should be greater than xupsEnvRemoteHumidityLowerLimit.

What is xupsEnvRemoteHumidityUpperLimit?

This is the configurable high-humidity threshold paired with xupsEnvRemoteHumidityLowerLimit. Exceeding it fires the xupsRemoteHumidityBad alarm, warning admins of condensation risk from a leak, failed dehumidifier, or HVAC issue in the monitored space. Setting it to 70 percent alerts staff if moisture rises high enough to threaten corrosion or condensation on equipment.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.534.1.6.12
snmpwalk -v2c -c public <target> EATON-EMP-MIB::xupsEnvRemoteHumidityUpperLimit

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.534.1.6.12.1
snmpget -v2c -c public <target> EATON-EMP-MIB::xupsEnvRemoteHumidityUpperLimit.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.534.1.6.12.1 i <value>

Start monitoring Eaton UPS/power equipment with Environmental Monitoring Probe (EMP) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-EMP-MIB::xupsEnvRemoteHumidityUpperLimit OID value, configure state conditions and alerts, and monitor any Eaton UPS/power equipment with Environmental Monitoring Probe (EMP) from a single console.

OID Breakdown

Upper-level ancestors (9 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.534eatonEATON-OIDS
1.3.6.1.4.1.534.1xupsMIBEATON-OIDS
1.3.6.1.4.1.534.1.6xupsEnvironmentEATON-OIDS
Numeric OIDNameModule
1.3.6.1.4.1.534.1.6.12xupsEnvRemoteHumidityUpperLimitEATON-EMP-MIB