| OID symbolic | OID numeric | Type | Access | Description |
| INT acFail | 1.3.6.1.4.1.49136.1.3.2 | INTEGER | read-only | Alarm that alert about AC outages in the last 10
minutes:
0 - DC-UPS in normal operation.
1 - Occur a AC fail in the last 10 minutes. |
| INT alarmOnBattery | 1.3.6.1.4.1.49136.1.3.1 | INTEGER | read-only | Shows the operation mode of DC-UPS:
0 - The DC-UPS output is provide by AC energy.
1 - The DC-UPS output is provide by Battery |
| algcom | 1.3.6.1.4.1.49136 | | | |
| bat_tst | 1.3.6.1.4.1.49136.1.8 | | | |
| STR batBrand | 1.3.6.1.4.1.49136.1.7.6 | DisplayString | read-only | Battery brand |
| INT batCapacity | 1.3.6.1.4.1.49136.1.7.5 | INTEGER | read-only | Battery capacity |
| STR batInstDate | 1.3.6.1.4.1.49136.1.7.7 | DisplayString | read-only | Battery installation date |
| battery | 1.3.6.1.4.1.49136.1.2 | | | |
| INT batteryCharging | 1.3.6.1.4.1.49136.1.3.3 | INTEGER | read-only | Show the status of charging Battery:
1 - The battery is on charging.
0 - The battery is on discharging. |
| INT batteryCurrent | 1.3.6.1.4.1.49136.1.2.2 | INTEGER | read-only | Numeric value of current in Battery bank. Real
value reading in milli ampere.
If the value is negative the Battery bank is provide
energy for the output.
If the value is positive the Battery bank is under
charger
Example:
Read value -2230, Actual value 2,230 ampere and the
battery bank is provide this current.
Read value 3000, Actual value 3.000 milli ampere and
the battery bank is absorve this current. |
| INT batteryDischarging | 1.3.6.1.4.1.49136.1.3.4 | INTEGER | read-only | Show the status of discharging Battery:
1 - The battery is on discharging.
0 - The battery is on charging. |
| INT batteryVoltage | 1.3.6.1.4.1.49136.1.2.1 | INTEGER | read-only | Numeric value of instantaneous voltage of battery bank.
To get the actual value in volt must be divided by 10.
Example:
Read value 240, actual value 24.0V. |
| INT btst_amp_f | 1.3.6.1.4.1.49136.1.8.8 | INTEGER | read-only | The battery initial cuurent [mA] Numeric value of battery current when the battery test is done. Example: Read value 1485, actual value 1.48 A. |
| INT btst_amp_i | 1.3.6.1.4.1.49136.1.8.6 | INTEGER | read-only | The battery initial cuurent [mA] Numeric value of battery current when starting the battery test. Example: Read value 1522, actual value 1.55 A. |
| STR btst_date | 1.3.6.1.4.1.49136.1.8.1 | DisplayString | read-only | Battery test execution date (dd/mm/yyyy) |
| INT btst_duration | 1.3.6.1.4.1.49136.1.8.3 | INTEGER | read-only | Programmed test duration in minutes * 999 - Perform the test until battery is fully discharged |
| INT btst_elapsed | 1.3.6.1.4.1.49136.1.8.4 | INTEGER | read-only | Elapsed time in current\last battery test |
| INT btst_status | 1.3.6.1.4.1.49136.1.8.2 | INTEGER | read-only | Battery test status 0 - NEVER DONE 1 - Passed 2 - Running 3 - Aborted 4 - Failed |
| INT btst_volt_f | 1.3.6.1.4.1.49136.1.8.7 | INTEGER | read-only | The battery final voltage [dV] Numeric value of battery voltage when the battery test is done. Example: Read value 225, actual value 22.5 V. |
| INT btst_volt_i | 1.3.6.1.4.1.49136.1.8.5 | INTEGER | read-only | The battery initial voltage [dV] Numeric value of battery voltage when starting the battery test. Example: Read value 241, actual value 24.1 V. |
| INT chargerStatus | 1.3.6.1.4.1.49136.1.2.3 | INTEGER | read-only | Show the status of battery charger:
0 - The battery is not connected in DC UPS;
1 - The battery is voltage incompatible with DC UPS;
2 - The DC UPS is in nobreak mode;
3 - The charger of Battery is in Bulk stage;
4 - The charger of Battery is Absorption stage;
5 - The charger of Battery is Float stage;
6 - The Battery will be disconnected in 30s due to
low voltage and the DC-UPS output will be
turned off.
7 - The Battery is under test |
| STR facilityAddr | 1.3.6.1.4.1.49136.1.7.2 | DisplayString | read-only | Facility address |
| STR facilityCity | 1.3.6.1.4.1.49136.1.7.3 | DisplayString | read-only | Facility city |
| INT fanAfail | 1.3.6.1.4.1.49136.1.3.7 | INTEGER | read-only | Alarm that alert about fail in internal FAN A
1 - Internal FAN with fail.
0 - Internal FAN ok |
| INT fanBfail | 1.3.6.1.4.1.49136.1.3.8 | INTEGER | read-only | Alarm that alert about fail in internal FAN B
1 - Internal FAN with fail.
0 - Internal FAN ok |
| INT heatSinkTemperature | 1.3.6.1.4.1.49136.1.4.3 | INTEGER | read-only | Show the temperature of sensor in the heatsink of
power supply use the unit degree Celsius.
Example
Read value: 25, temperature is 25degC. |
| INT innerTemperature | 1.3.6.1.4.1.49136.1.4.1 | INTEGER | read-only | Show the internal temperature of power supply.
Uses the unit degree Celsius.
Example
Read value: 25, temperature is 25degC. |
| input | 1.3.6.1.4.1.49136.1.3 | | | |
| installation | 1.3.6.1.4.1.49136.1.7 | | | |
| STR instDate | 1.3.6.1.4.1.49136.1.7.4 | DisplayString | read-only | Installation date |
| INT oidNotUsed0 | 1.3.6.1.4.1.49136.1.1.3 | INTEGER | read-only | OID not used. |
| INT oidNotUsed1 | 1.3.6.1.4.1.49136.1.1.4 | INTEGER | read-only | OID not used. |
| INT oidNotUsed2 | 1.3.6.1.4.1.49136.1.3.9 | INTEGER | read-only | OID not used. |
| INT oidNotUsed3 | 1.3.6.1.4.1.49136.1.3.10 | INTEGER | read-only | OID not used. |
| INT outerTemperature | 1.3.6.1.4.1.49136.1.4.2 | INTEGER | read-only | Show the temperature of external sensor (cable that
comes with power supply).
Uses the unit degree Celsius.
Example
Read value: 25, temperature is 25degC. |
| output | 1.3.6.1.4.1.49136.1.1 | | | |
| INT outputCurrent | 1.3.6.1.4.1.49136.1.1.2 | INTEGER | read-only | Numeric value of current output of converter AC/DC.
Real value reading in milli ampere.
Example:
Read value 1087, Actual value 1.087 milli ampere
or 1.087A.
If the output is '0' the AC/DC is off and the output
for the equipments is provide from batteries |
| INT outputVoltage | 1.3.6.1.4.1.49136.1.1.1 | INTEGER | read-only | Numeric value of instantaneous output voltage from
the source in tenths of a volt. To get the value
actual in volt should be divided by 10.
Example:
Read value 241, actual value 24.1V. |
| INT overheat | 1.3.6.1.4.1.49136.1.3.5 | INTEGER | read-only | Alarm that alert about overtemperature of DC-UPS
1 - The DC-UPS is in condition of overtemperature.
0 - The DC-UPS is in normal condition. |
| INT overload | 1.3.6.1.4.1.49136.1.3.6 | INTEGER | read-only | Alarm that alert about overload of DC-UPS
1 - The DC-UPS is in condition of overload.
0 - The DC-UPS is in normal condition. |
| STR popName | 1.3.6.1.4.1.49136.1.7.1 | DisplayString | read-only | PoP name |
| STR respPers | 1.3.6.1.4.1.49136.1.7.8 | DisplayString | read-only | Responsible person |
| supply | 1.3.6.1.4.1.49136.1.6 | | | |
| INT supplyVoltage | 1.3.6.1.4.1.49136.1.6.1 | INTEGER | read-only | The supply AC voltage decivolt [dV]
Numeric value of instantaneous input voltage.
An optional sensor is required to read this value.
To get the actual value in volt it should be
divided by 10.
Example:
Read value 2410, actual value 241 Vac. |
| temperature | 1.3.6.1.4.1.49136.1.4 | | | |
| upsObjects | 1.3.6.1.4.1.49136.1 | | | |
| INT upTime | 1.3.6.1.4.1.49136.1.3.11 | INTEGER | read-only | System Up time in hours |
| watchdog | 1.3.6.1.4.1.49136.1.5 | | | |
| INT watchdogPing1 | 1.3.6.1.4.1.49136.1.5.1 | INTEGER | read-only | Alarm indicating the action of watchdog 1
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 1 acted on the output the last 10
minutes.
0 - The Watchdog 1 has not acted in the last 10
minutes. |
| INT watchdogPing10 | 1.3.6.1.4.1.49136.1.5.10 | INTEGER | read-only | Alarm indicating the action of watchdog 10
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 10 acted on the output the last 10
minutes.
0 - The Watchdog 10 has not acted in the last 10
minutes. |
| INT watchdogPing2 | 1.3.6.1.4.1.49136.1.5.2 | INTEGER | read-only | Alarm indicating the action of watchdog 2
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 2 acted on the output the last 10
minutes.
0 - The Watchdog 2 has not acted in the last 10
minutes. |
| INT watchdogPing3 | 1.3.6.1.4.1.49136.1.5.3 | INTEGER | read-only | Alarm indicating the action of watchdog 3
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 3 acted on the output the last 10
minutes.
0 - The Watchdog 3 has not acted in the last 10
minutes. |
| INT watchdogPing4 | 1.3.6.1.4.1.49136.1.5.4 | INTEGER | read-only | Alarm indicating the action of watchdog 4
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 4 acted on the output the last 10
minutes.
0 - The Watchdog 4 has not acted in the last 10
minutes. |
| INT watchdogPing5 | 1.3.6.1.4.1.49136.1.5.5 | INTEGER | read-only | Alarm indicating the action of watchdog 5
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 5 acted on the output the last 10
minutes.
0 - The Watchdog 5 has not acted in the last 10
minutes. |
| INT watchdogPing6 | 1.3.6.1.4.1.49136.1.5.6 | INTEGER | read-only | Alarm indicating the action of watchdog 6
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 6 acted on the output the last 10
minutes.
0 - The Watchdog 6 has not acted in the last 10
minutes. |
| INT watchdogPing7 | 1.3.6.1.4.1.49136.1.5.7 | INTEGER | read-only | Alarm indicating the action of watchdog 7
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 7 acted on the output the last 10
minutes.
0 - The Watchdog 7 has not acted in the last 10
minutes. |
| INT watchdogPing8 | 1.3.6.1.4.1.49136.1.5.8 | INTEGER | read-only | Alarm indicating the action of watchdog 8
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 8 acted on the output the last 10
minutes.
0 - The Watchdog 8 has not acted in the last 10
minutes. |
| INT watchdogPing9 | 1.3.6.1.4.1.49136.1.5.9 | INTEGER | read-only | Alarm indicating the action of watchdog 9
programmed in the last 10 minutes. The watchdog
acts on the output by turning it off when not
receive response from IP ping command
configured.
1 - The watchdog 9 acted on the output the last 10
minutes.
0 - The Watchdog 9 has not acted in the last 10
minutes. |