XPPC-MIB :: upsSmartControlSimulatePowerFail

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › XPPC-MIB › upsSmartControlSimulatePowerFail

upsSmartControlSimulatePowerFail

Module: XPPC-MIB

OID (symbolic): XPPC-MIB::upsSmartControlSimulatePowerFail

OID (numeric): 1.3.6.1.4.1.935.1.1.1.6.2.4

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: Setting this variable to simulatePowerFailure(2) causes the UPS switch to battery power.

Setting this value to noSimulatePowerFailure(1) has no effect.

The value noSimulatePowerFailure(1) will always be returned when the variable is read.

What is upsSmartControlSimulatePowerFail?

Writing simulatePowerFailure(2) forces the UPS to switch over to battery power even though utility power is present, letting an admin test the battery-transfer behavior on demand; reading this object always returns the no-op value noSimulatePowerFailure(1).

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.935.1.1.1.6.2.4
snmpwalk -v2c -c public <target> XPPC-MIB::upsSmartControlSimulatePowerFail

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.935.1.1.1.6.2.4.1
snmpget -v2c -c public <target> XPPC-MIB::upsSmartControlSimulatePowerFail.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.935.1.1.1.6.2.4.1 i <value>

Start monitoring Vendor UPS/power-management appliance, PPC product line (trap-receiver config, UPS model/firmware status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the XPPC-MIB::upsSmartControlSimulatePowerFail OID value, configure state conditions and alerts, and monitor any Vendor UPS/power-management appliance, PPC product line (trap-receiver config, UPS model/firmware status) from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.935ppcEPPC-MIB
Numeric OIDNameModule
1.3.6.1.4.1.935.1productsXPPC-MIB
1.3.6.1.4.1.935.1.1hardwareXPPC-MIB
1.3.6.1.4.1.935.1.1.1upsXPPC-MIB
1.3.6.1.4.1.935.1.1.1.6upsControlpXPPC-MIB
1.3.6.1.4.1.935.1.1.1.6.2upsSmartControlXPPC-MIB
1.3.6.1.4.1.935.1.1.1.6.2.4upsSmartControlSimulatePowerFailXPPC-MIB