upsSmartConfigMinReturnCapacity

Module: XPPC-MIB

OID (symbolic): XPPC-MIB::upsSmartConfigMinReturnCapacity

OID (numeric): 1.3.6.1.4.1.935.1.1.1.5.2.6

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: The minimum battery capacity as a percent of full capacity required before the UPS will return from a low battery shutdown condition. In other words, the UPS will not re-energize the output until the battery capacity is equal to this value. Allowed values are 0, 10, 25, or 90 percent.

If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.935.1.1.1.5.2.6
snmpwalk -v2c -c public <target> XPPC-MIB::upsSmartConfigMinReturnCapacity

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.935.1.1.1.5.2.6.1
snmpget -v2c -c public <target> XPPC-MIB::upsSmartConfigMinReturnCapacity.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.935.1.1.1.5.2.6.1 i <value>

Start monitoring Vendor UPS/power-management appliance, PPC product line (trap-receiver config, UPS model/firmware status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the XPPC-MIB::upsSmartConfigMinReturnCapacity OID value, configure state conditions and alerts, and monitor any Vendor UPS/power-management appliance, PPC product line (trap-receiver config, UPS model/firmware status) from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.935ppcTELECOM-MIB
Numeric OIDNameModule
1.3.6.1.4.1.935.1productsXPPC-MIB
1.3.6.1.4.1.935.1.1hardwareXPPC-MIB
1.3.6.1.4.1.935.1.1.1upsXPPC-MIB
1.3.6.1.4.1.935.1.1.1.5upsConfigpXPPC-MIB
1.3.6.1.4.1.935.1.1.1.5.2upsSmartConfigXPPC-MIB
1.3.6.1.4.1.935.1.1.1.5.2.6upsSmartConfigMinReturnCapacityXPPC-MIB