XPPC-MIB :: upsSmartConfigLowTransferVolt

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsXPPC-MIBupsSmartConfigLowTransferVolt

upsSmartConfigLowTransferVolt

Module: XPPC-MIB

OID (symbolic): XPPC-MIB::upsSmartConfigLowTransferVolt

OID (numeric): 1.3.6.1.4.1.935.1.1.1.5.2.3

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: The minimum line voltage in 1/10 VAC allowed before the UPS system transfers to battery backup.

Allowable values depend on the UPS used: 120 Volt units allow settings of 970, 1000, 1030, 1060. 100 Volt units allow settings of 810, 830, 850, 870. 230 Volt units allow settings of 1880, 1960, 2040, 2080. 208 Volt units allow settings of 1680, 1720, 1770, 1820.

If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.935.1.1.1.5.2.3
snmpwalk -v2c -c public <target> XPPC-MIB::upsSmartConfigLowTransferVolt

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.935.1.1.1.5.2.3.1
snmpget -v2c -c public <target> XPPC-MIB::upsSmartConfigLowTransferVolt.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.935.1.1.1.5.2.3.1 i <value>

Start monitoring Vendor UPS/power-management appliance, PPC product line (trap-receiver config, UPS model/firmware status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the XPPC-MIB::upsSmartConfigLowTransferVolt OID value, configure state conditions and alerts, and monitor any Vendor UPS/power-management appliance, PPC product line (trap-receiver config, UPS model/firmware status) from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.935ppcTELECOM-MIB
Numeric OIDNameModule
1.3.6.1.4.1.935.1productsXPPC-MIB
1.3.6.1.4.1.935.1.1hardwareXPPC-MIB
1.3.6.1.4.1.935.1.1.1upsXPPC-MIB
1.3.6.1.4.1.935.1.1.1.5upsConfigpXPPC-MIB
1.3.6.1.4.1.935.1.1.1.5.2upsSmartConfigXPPC-MIB
1.3.6.1.4.1.935.1.1.1.5.2.3upsSmartConfigLowTransferVoltXPPC-MIB