All MIBs › XPPC-MIB › upsSmartConfigLowBatteryRunTime
upsSmartConfigLowBatteryRunTime
Module: XPPC-MIB
OID (symbolic): XPPC-MIB::upsSmartConfigLowBatteryRunTime
OID (numeric): 1.3.6.1.4.1.935.1.1.1.5.2.8
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: The desired run time in seconds once the low battery condition is reached. Allowed values are 120, 300, 420, or 600 seconds. During this time the UPS will produce a constant warning tone which can not be disabled.
If a value other than a supported value is provided in a set request, the UPS interprets it as a the next higher acceptable value. If the provided value is higher than the highest acceptable value, the highest acceptable value is used.
What is upsSmartConfigLowBatteryRunTime?
Sets how many seconds of runtime the UPS reserves once it declares a low-battery condition, from the allowed set 120/300/420/600 seconds; during this reserved window the UPS emits a constant, non-disableable warning tone. A larger value gives more shutdown warning time but leaves less usable runtime before the low-battery threshold is hit.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.935.1.1.1.5.2.8 snmpwalk -v2c -c public <target> XPPC-MIB::upsSmartConfigLowBatteryRunTime
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.935.1.1.1.5.2.8.1 snmpget -v2c -c public <target> XPPC-MIB::upsSmartConfigLowBatteryRunTime.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.935.1.1.1.5.2.8.1 i <value>
Start monitoring Vendor UPS/power-management appliance, PPC product line (trap-receiver config, UPS model/firmware status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the XPPC-MIB::upsSmartConfigLowBatteryRunTime OID value, configure state conditions and alerts, and monitor any Vendor UPS/power-management appliance, PPC product line (trap-receiver config, UPS model/firmware status) from a single console.
OID Breakdown
Upper-level ancestors (7 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.935 | ppc | EPPC-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.935.1 | products | XPPC-MIB |
| 1.3.6.1.4.1.935.1.1 | hardware | XPPC-MIB |
| 1.3.6.1.4.1.935.1.1.1 | ups | XPPC-MIB |
| 1.3.6.1.4.1.935.1.1.1.5 | upsConfigp | XPPC-MIB |
| 1.3.6.1.4.1.935.1.1.1.5.2 | upsSmartConfig | XPPC-MIB |
| 1.3.6.1.4.1.935.1.1.1.5.2.8 | upsSmartConfigLowBatteryRunTime | XPPC-MIB |