All MIBs › WebGraph-Thermo-Hygrometer-MIB › wtWebGraphThermHygroAlarmHysteresis
wtWebGraphThermHygroAlarmHysteresis
Module: WebGraph-Thermo-Hygrometer-MIB
OID (symbolic): WebGraph-Thermo-Hygrometer-MIB::wtWebGraphThermHygroAlarmHysteresis
OID (numeric): 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.4
Node type: OBJECT-TYPE
Type: OCTET STRING
Access: read-write
Description: Bei Uberschreiten der Temperatur Min+Hyst. und Unterschreiten der Temperatur Max-Hyst. wird der Alarm geloscht: pos. Temperaturdifferenz in Grad mit maximal 2 Nachkommastellen.
What is wtWebGraphThermHygroAlarmHysteresis?
Sets a positive temperature-difference margin (in degrees) that must be crossed back past the min/max thresholds before the alarm is cleared, e.g. the temperature must rise above Min+Hysteresis or fall below Max-Hysteresis. This prevents the alarm from rapidly flapping on and off when a reading hovers right at the threshold.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.4 snmpwalk -v2c -c public <target> WebGraph-Thermo-Hygrometer-MIB::wtWebGraphThermHygroAlarmHysteresis
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.4.1 snmpget -v2c -c public <target> WebGraph-Thermo-Hygrometer-MIB::wtWebGraphThermHygroAlarmHysteresis.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.4.1 s <value>
Start monitoring WebGraph thermo-hygrometer environmental sensor (temperature/humidity reading/threshold-alarm status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the WebGraph-Thermo-Hygrometer-MIB::wtWebGraphThermHygroAlarmHysteresis OID value, configure state conditions and alerts, and monitor any WebGraph thermo-hygrometer environmental sensor (temperature/humidity reading/threshold-alarm status) from a single console.
OID Breakdown
Upper-level ancestors (15 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.5040 | wut | Com-Server-Intern-MIB |
| 1.3.6.1.4.1.5040.1 | wtComServer | Com-Server-Intern-MIB |
| 1.3.6.1.4.1.5040.1.2 | wtWebio | WebGraph-8xThermometer-US-MIB |
| 1.3.6.1.4.1.5040.1.2.9 | wtWebGraphThermHygro | WebGraph-OLD-Thermo-Hygrometer-US-MIB |
| 1.3.6.1.4.1.5040.1.2.9.3 | wtWebGraphThermHygroConfig | WebGraph-OLD-Thermo-Hygrometer-US-MIB |
| 1.3.6.1.4.1.5040.1.2.9.3.1 | wtWebGraphThermHygroDevice | WebGraph-OLD-Thermo-Hygrometer-US-MIB |
| 1.3.6.1.4.1.5040.1.2.9.3.1.5 | wtWebGraphThermHygroAlarm | WebGraph-OLD-Thermo-Hygrometer-US-MIB |
| 1.3.6.1.4.1.5040.1.2.9.3.1.5.3 | wtWebGraphThermHygroAlarmTable | WebGraph-OLD-Thermo-Hygrometer-US-MIB |
| 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1 | wtWebGraphThermHygroAlarmEntry | WebGraph-OLD-Thermo-Hygrometer-US-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.5040.1.2.9.3.1.5.3.1.4 | wtWebGraphThermHygroAlarmHysteresis | WebGraph-Thermo-Hygrometer-MIB |