All MIBs › TRIPPUPS1-MIB › upsRebootDuration
upsRebootDuration
Module: TRIPPUPS1-MIB
OID (symbolic): TRIPPUPS1-MIB::upsRebootDuration
OID (numeric): 1.3.6.1.4.1.850.1.1.9.4
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Setting this object will immediately shutdown (i.e., turn off) either the UPS output or the UPS system (as determined by the value of the upsShutdownType at the time of shutdown) for a period equal to the indicated number of seconds, after which time the output will be started, including starting the UPS, if necessary. If the number of seconds required to perform the request is greater than the requested duration, then the requested shutdown and startup cycle shall be performed in the minimum time possible, but in no case shall this require more than the requested duration plus 60 seconds. When read, upsRebootDuration shall return the number of seconds remaining in the countdown, or -1 if no countdown is in progress. If the startup should occur during a utility failure, the startup shall depend on the value of upsAutoRestart at that time. UNITS seconds
What is upsRebootDuration?
Immediately shuts down the UPS output or system for the specified number of seconds and then restarts it, effectively power-cycling connected equipment; setting -1 means no reboot countdown is active, and reading the object returns the seconds remaining in the cycle.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.850.1.1.9.4 snmpwalk -v2c -c public <target> TRIPPUPS1-MIB::upsRebootDuration
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.850.1.1.9.4.1 snmpget -v2c -c public <target> TRIPPUPS1-MIB::upsRebootDuration.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.850.1.1.9.4.1 i <value>
Start monitoring Tripp Lite uninterruptible power supply (UPS) units (battery temperature/input-voltage/output-load status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the TRIPPUPS1-MIB::upsRebootDuration OID value, configure state conditions and alerts, and monitor any Tripp Lite uninterruptible power supply (UPS) units (battery temperature/input-voltage/output-load status) from a single console.
OID Breakdown
Upper-level ancestors (9 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.850 | tripplite | TRIPPLITE |
| 1.3.6.1.4.1.850.1 | trippUPS | TRIPPLITE-MIB |
| 1.3.6.1.4.1.850.1.1 | trippUpsReceptacles | TRIPPLITE-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.850.1.1.9 | upsControl | TRIPPUPS1-MIB |
| 1.3.6.1.4.1.850.1.1.9.4 | upsRebootDuration | TRIPPUPS1-MIB |