All MIBs › SOCOMECUPS-MIB › upsTestResultsSummary
upsTestResultsSummary
Module: SOCOMECUPS-MIB
OID (symbolic): SOCOMECUPS-MIB::upsTestResultsSummary
OID (numeric): 1.3.6.1.4.1.4555.1.1.1.1.7.3
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: The results of the current or last UPS diagnostics test performed. The values for donePass(1), doneWarning(2), and doneError(3) indicate that the test completed either successfully, with a warning, or with an error, respectively. The value aborted(4) is returned for tests which are aborted by setting the value of upsTestId to upsTestAbortTestInProgress. Tests which have not yet concluded are indicated by inProgress(5). The value noTestsInitiated(6) indicates that no previous test results are available, such as is the case when no tests have been run since the last reinitialization of the network management subsystem and the system has no provision for non- volatile storage of test results.
What is upsTestResultsSummary?
Reports the outcome of the current or most recent UPS diagnostic test. Note the source MIB's own DESCRIPTION text (mentioning donePass/doneWarning/doneError/aborted/inProgress/noTestsInitiated) doesn't match the actual defined SYNTAX enumeration, which is notActive(1), inProgress(2), byPass(3), failed(4) -- this is an inconsistency in the source MIB itself, so an admin should trust the actual enumerated values (e.g. inProgress(2), failed(4)) returned by the agent rather than the prose description.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.4555.1.1.1.1.7.3 snmpwalk -v2c -c public <target> SOCOMECUPS-MIB::upsTestResultsSummary
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.4555.1.1.1.1.7.3.1 snmpget -v2c -c public <target> SOCOMECUPS-MIB::upsTestResultsSummary.1
Start monitoring Socomec UPS, power protection equipment (battery/input-output/alarm status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the SOCOMECUPS-MIB::upsTestResultsSummary OID value, configure state conditions and alerts, and monitor any Socomec UPS, power protection equipment (battery/input-output/alarm status) from a single console.
OID Breakdown
Upper-level ancestors (7 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.4555 | socomec | SOCOMECPDU-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.4555.1 | software | SOCOMECUPS-MIB |
| 1.3.6.1.4.1.4555.1.1 | network | SOCOMECUPS-MIB |
| 1.3.6.1.4.1.4555.1.1.1 | netvision | SOCOMECUPS-MIB |
| 1.3.6.1.4.1.4555.1.1.1.1 | upsObjects | SOCOMECUPS-MIB |
| 1.3.6.1.4.1.4555.1.1.1.1.7 | upsTest | SOCOMECUPS-MIB |
| 1.3.6.1.4.1.4555.1.1.1.1.7.3 | upsTestResultsSummary | SOCOMECUPS-MIB |