All MIBs › SL61-STD-MIB › esPointInEventState
esPointInEventState
Module: SL61-STD-MIB
OID (symbolic): SL61-STD-MIB::esPointInEventState
OID (numeric): 1.3.6.1.4.1.3052.4.1.1.1.1.5
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: A number referring to the event state of a point on an EventSensor. This number can have different meanings depending on the point class.
If the point class is temperature, humidity, or analog input, then the values of this object are: 1=very low 2=low 3=normal 4=high 5=very high
For contact closures and relays the values of this object are: 1=point in event state 2=point in normal state
For any point class and any point, if the event state is undefined, then the value of this object is 0.
For any point class except relay, this object is read-only. For relays, setting this object to 1 puts the relay into its event (active) state. Setting it to 2 puts the relay into its normal (inactive) state. Depending on how the relay's active state is configured in the setup menu, the relay will then open or close. This works regardless of the control mode of the relay.
What is esPointInEventState?
The current event state of this point: for temperature/humidity/analog points, 1=very low through 5=very high (0 if undefined); for contact closures and relays, 1=in event state or 2=in normal state. Only relays are writable here, letting an admin manually force a relay open or closed regardless of its configured control mode.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3052.4.1.1.1.1.5 snmpwalk -v2c -c public <target> SL61-STD-MIB::esPointInEventState
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.3052.4.1.1.1.1.5.1 snmpget -v2c -c public <target> SL61-STD-MIB::esPointInEventState.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.3052.4.1.1.1.1.5.1 i <value>
Start monitoring Omnitronix SL61 remote-site environmental monitoring unit (event-sensor/pager alarm status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the SL61-STD-MIB::esPointInEventState OID value, configure state conditions and alerts, and monitor any Omnitronix SL61 remote-site environmental monitoring unit (event-sensor/pager alarm status) from a single console.
OID Breakdown
Upper-level ancestors (7 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.3052 | asentria | ASENTRIA-ROOT-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.3052.4 | sl61 | SL61-STD-MIB |
| 1.3.6.1.4.1.3052.4.1 | status | SL61-STD-MIB |
| 1.3.6.1.4.1.3052.4.1.1 | eventSensorStatus | SL61-STD-MIB |
| 1.3.6.1.4.1.3052.4.1.1.1 | esPointTable | SL61-STD-MIB |
| 1.3.6.1.4.1.3052.4.1.1.1.1 | esPointEntry | SL61-STD-MIB |
| 1.3.6.1.4.1.3052.4.1.1.1.1.5 | esPointInEventState | SL61-STD-MIB |