RITTAL-CMC-TC-MIB :: unit3OutputType

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › RITTAL-CMC-TC-MIB › unit3OutputType

unit3OutputType

Module: RITTAL-CMC-TC-MIB

OID (symbolic): RITTAL-CMC-TC-MIB::unit3OutputType

OID (numeric): 1.3.6.1.4.1.2606.4.2.5.6.2.1.2

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: Type of output which is connected to sensor unit 3 to output[unit3OutputIndex] 1: no output connected 2: output failure 3: value overflow 4: output type 1, door locking TS8,Ergoform 5: output type 2, universal lock 1, lock with power 6: output type 3, universal lock 2, unlock with power 7: output type 4, fan relay 8: output type 5, fan controlled 9: output type 6, universal relay output 10: output type 7, room door lock 11: output type 8, power output 12: output type 9, door lock with Master key 13: output type 10, door lock FR(i) 14: setpoint (FCS, RTT) 15: setpoint temperature monitoring (RTT)

What is unit3OutputType?

What kind of output type (15 possible values covering door locks, universal relays, fan control, power outputs, and RTT/FCS setpoints) this row on unit 3 controls. Knowing the type tells an admin what unit3OutputSet actually does when written for that row, for example locking a door versus switching a fan.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.2606.4.2.5.6.2.1.2
snmpwalk -v2c -c public <target> RITTAL-CMC-TC-MIB::unit3OutputType

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.2606.4.2.5.6.2.1.2.1
snmpget -v2c -c public <target> RITTAL-CMC-TC-MIB::unit3OutputType.1

SNMPv3 example:

snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> unit3OutputType.1

Start monitoring Rittal CMC (Computer Multi Control) rack environmental monitoring unit (shared textual conventions) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the RITTAL-CMC-TC-MIB::unit3OutputType OID value, configure state conditions and alerts, and monitor any Rittal CMC (Computer Multi Control) rack environmental monitoring unit (shared textual conventions) from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.2606rittalRITTAL-CMC-TC-MIB
1.3.6.1.4.1.2606.4cmcTcRITTAL-CMC-TC-MIB
1.3.6.1.4.1.2606.4.2cmcTcStatusRITTAL-CMC-TC-MIB
1.3.6.1.4.1.2606.4.2.5cmcTcStatusSensorUnit3RITTAL-CMC-TC-MIB
1.3.6.1.4.1.2606.4.2.5.6cmcTcStatusUnit3OutputsRITTAL-CMC-TC-MIB
1.3.6.1.4.1.2606.4.2.5.6.2cmcTcUnit3OutputTableRITTAL-CMC-TC-MIB
1.3.6.1.4.1.2606.4.2.5.6.2.1cmcTcUnit3OutputEntryRITTAL-CMC-TC-MIB
1.3.6.1.4.1.2606.4.2.5.6.2.1.2unit3OutputTypeRITTAL-CMC-TC-MIB