PDU-MIB :: dataLogMaxCircuitBreakerCurrent

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › PDU-MIB › dataLogMaxCircuitBreakerCurrent

dataLogMaxCircuitBreakerCurrent

Module: PDU-MIB

OID (symbolic): PDU-MIB::dataLogMaxCircuitBreakerCurrent

OID (numeric): 1.3.6.1.4.1.13742.4.1.15.1.1.4

Node type: OBJECT-TYPE

Type: MilliAmps

Access: read-only

Description: The Maximum value for the measurement period: The value of the current reported in MilliAmps.

What is dataLogMaxCircuitBreakerCurrent?

Maximum current through this circuit breaker during the data log entry's measurement period, in milliamps. Useful for identifying peak branch-circuit load that might risk a future trip.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.13742.4.1.15.1.1.4
snmpwalk -v2c -c public <target> PDU-MIB::dataLogMaxCircuitBreakerCurrent

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.13742.4.1.15.1.1.4.1
snmpget -v2c -c public <target> PDU-MIB::dataLogMaxCircuitBreakerCurrent.1

Start monitoring Raritan Dominion PX intelligent power distribution unit (PDU) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the PDU-MIB::dataLogMaxCircuitBreakerCurrent OID value, configure state conditions and alerts, and monitor any Raritan Dominion PX intelligent power distribution unit (PDU) from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.13742raritanASSETMANAGEMENT-MIB
Numeric OIDNameModule
1.3.6.1.4.1.13742.4pduPDU-MIB
1.3.6.1.4.1.13742.4.1boardPDU-MIB
1.3.6.1.4.1.13742.4.1.15dataLogCircuitBreakerPDU-MIB
1.3.6.1.4.1.13742.4.1.15.1dataLogCircuitBreakerTablePDU-MIB
1.3.6.1.4.1.13742.4.1.15.1.1dataLogCircuitBreakerEntryPDU-MIB
1.3.6.1.4.1.13742.4.1.15.1.1.4dataLogMaxCircuitBreakerCurrentPDU-MIB