LIEBERT-UPSTATION-D-UPS-MIB :: ldUpsInputMaxVoltsSinceLastPoll

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsLIEBERT-UPSTATION-D-UPS-MIBldUpsInputMaxVoltsSinceLastPoll

ldUpsInputMaxVoltsSinceLastPoll

Module: LIEBERT-UPSTATION-D-UPS-MIB

OID (symbolic): LIEBERT-UPSTATION-D-UPS-MIB::ldUpsInputMaxVoltsSinceLastPoll

OID (numeric): 1.3.6.1.4.1.476.1.1.1.3.3.1

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: The maximum input voltage encountered since the object was last retrieved. Note: if there are multiple managers talking to the same agent, the use of this object needs to be coordinated.

What is ldUpsInputMaxVoltsSinceLastPoll?

The highest input voltage seen since this object was last read; because the value resets on each poll, an admin sharing this UPS across multiple monitoring systems needs to coordinate polling to avoid one manager's read erasing data another manager expected to see.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.3.3.1
snmpwalk -v2c -c public <target> LIEBERT-UPSTATION-D-UPS-MIB::ldUpsInputMaxVoltsSinceLastPoll

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.1.1.3.3.1.1
snmpget -v2c -c public <target> LIEBERT-UPSTATION-D-UPS-MIB::ldUpsInputMaxVoltsSinceLastPoll.1

Start monitoring Liebert (Vertiv) UPStation D series UPS with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-UPSTATION-D-UPS-MIB::ldUpsInputMaxVoltsSinceLastPoll OID value, configure state conditions and alerts, and monitor any Liebert (Vertiv) UPStation D series UPS from a single console.

OID Breakdown

Upper-level ancestors (12 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.1liebertUpsLIEBERT-MICRO-UPS-MIB
1.3.6.1.4.1.476.1.1.1luExtensionsLIEBERT-MICRO-UPS-MIB
1.3.6.1.4.1.476.1.1.1.3luUPStationDLIEBERT-UPS-MIB
1.3.6.1.4.1.476.1.1.1.3.3ldUpsInputLIEBERT-UPS-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.1.1.3.3.1ldUpsInputMaxVoltsSinceLastPollLIEBERT-UPSTATION-D-UPS-MIB