All MIBs › HM2-L2REDUNDANCY-MIB › hm2RingCplCouplingLinks
hm2RingCplCouplingLinks
Module: HM2-L2REDUNDANCY-MIB
OID (symbolic): HM2-L2REDUNDANCY-MIB::hm2RingCplCouplingLinks
OID (numeric): 1.3.6.1.4.1.248.11.40.1.8.1.1.14
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Maximum coupling links between two coupled rings in case of a failure in one of the coupled rings.
If there is no connection starting from the switch in slave or local operational state over the route of the coupled rings or nets to oneself the slave or the local mode want to set the coupling port in forwarding after a timeout period.
basicRedundancy(1) prevents the slave or the local mode from setting its coupling port into forwarding in case of the described failure. In this case the segment which is connected to this coupling port is unreachable until the failure is eliminated.
In extendedRedundancy(2) the coupling port and the partner coupling port are allowed to be in forwarding.
What is hm2RingCplCouplingLinks?
Chooses how the coupling handles a failure in one of the two coupled rings: basicRedundancy keeps the coupling port blocked (isolating the affected segment) while extendedRedundancy allows both the coupling port and its partner to forward, trading a stricter loop-prevention guarantee for wider reachability.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.248.11.40.1.8.1.1.14 snmpwalk -v2c -c public <target> HM2-L2REDUNDANCY-MIB::hm2RingCplCouplingLinks
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.248.11.40.1.8.1.1.14.1 snmpget -v2c -c public <target> HM2-L2REDUNDANCY-MIB::hm2RingCplCouplingLinks.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.248.11.40.1.8.1.1.14.1 i <value>
SNMPv3 example:
snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> hm2RingCplCouplingLinks.1
Start monitoring Hirschmann HiOS industrial Ethernet switch (MRP ring/RSTP redundancy) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the HM2-L2REDUNDANCY-MIB::hm2RingCplCouplingLinks OID value, configure state conditions and alerts, and monitor any Hirschmann HiOS industrial Ethernet switch (MRP ring/RSTP redundancy) from a single console.
OID Breakdown
Upper-level ancestors (8 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.248 | hirschmann | HM2-TC-MIB |
| 1.3.6.1.4.1.248.11 | hm2ConfigurationMibs | HM2-TC-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.248.11.40 | hm2L2RedundancyMib | HM2-L2REDUNDANCY-MIB |
| 1.3.6.1.4.1.248.11.40.1 | hm2L2RedundancyMibObjects | HM2-L2REDUNDANCY-MIB |
| 1.3.6.1.4.1.248.11.40.1.8 | hm2RingCouplingMibGroup | HM2-L2REDUNDANCY-MIB |
| 1.3.6.1.4.1.248.11.40.1.8.1 | hm2RingCouplingTable | HM2-L2REDUNDANCY-MIB |
| 1.3.6.1.4.1.248.11.40.1.8.1.1 | hm2RingCouplingEntry | HM2-L2REDUNDANCY-MIB |