ELTEK-DISTRIBUTED-PLANTV4-MIB :: batteryLVDConnectVoltage

MIB Reference — IPNetwork Monitor · Updated October 05, 2026

All MIBs › ELTEK-DISTRIBUTED-PLANTV4-MIB › batteryLVDConnectVoltage

batteryLVDConnectVoltage

Module: ELTEK-DISTRIBUTED-PLANTV4-MIB

OID (symbolic): ELTEK-DISTRIBUTED-PLANTV4-MIB::batteryLVDConnectVoltage

OID (numeric): 1.3.6.1.4.1.12148.9.3.17.3

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: The Battery Contactors Reconnect Voltage

What is batteryLVDConnectVoltage?

The battery voltage (1/100V units, 0-7200 range) at which the LVBD contactor recloses after having disconnected, once charging has restored voltage above this level. An admin sets this comfortably above batteryLVDDisconnectVoltage to avoid contactor chatter near the disconnect point.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.12148.9.3.17.3
snmpwalk -v2c -c public <target> ELTEK-DISTRIBUTED-PLANTV4-MIB::batteryLVDConnectVoltage

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.12148.9.3.17.3.1
snmpget -v2c -c public <target> ELTEK-DISTRIBUTED-PLANTV4-MIB::batteryLVDConnectVoltage.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.12148.9.3.17.3.1 i <value>

Start monitoring Eltek telecom DC power systems with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ELTEK-DISTRIBUTED-PLANTV4-MIB::batteryLVDConnectVoltage OID value, configure state conditions and alerts, and monitor any Eltek telecom DC power systems from a single console.

OID Breakdown

Upper-level ancestors (10 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.12148eltekELTEK-COMMON-MIB
1.3.6.1.4.1.12148.9eltekDistributedPlantV7ELTEK-DISTRIBUTED-MIB
1.3.6.1.4.1.12148.9.3batteryELTEK-DISTRIBUTED-MIB
1.3.6.1.4.1.12148.9.3.17batteryLVDELTEK-DISTRIBUTED-MIB
Numeric OIDNameModule