All MIBs › ELTEK-DISTRIBUTED-PLANTV4-MIB › batteryFloatVoltConfig
batteryFloatVoltConfig
Module: ELTEK-DISTRIBUTED-PLANTV4-MIB
OID (symbolic): ELTEK-DISTRIBUTED-PLANTV4-MIB::batteryFloatVoltConfig
OID (numeric): 1.3.6.1.4.1.12148.9.3.9
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: The Voltage at which the DC System float charges. Acts as reference voltage when running temperature compensated charging.
What is batteryFloatVoltConfig?
The float-charge voltage setpoint (1/100V units, e.g. 5400=54.00V), also used as the reference voltage when temperature-compensated charging is active. An admin tunes this to the battery manufacturer's recommended float voltage for the installed battery chemistry.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.12148.9.3.9 snmpwalk -v2c -c public <target> ELTEK-DISTRIBUTED-PLANTV4-MIB::batteryFloatVoltConfig
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.12148.9.3.9.1 snmpget -v2c -c public <target> ELTEK-DISTRIBUTED-PLANTV4-MIB::batteryFloatVoltConfig.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.12148.9.3.9.1 i <value>
Start monitoring Eltek telecom DC power systems with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the ELTEK-DISTRIBUTED-PLANTV4-MIB::batteryFloatVoltConfig OID value, configure state conditions and alerts, and monitor any Eltek telecom DC power systems from a single console.
OID Breakdown
Upper-level ancestors (9 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.12148 | eltek | ELTEK-COMMON-MIB |
| 1.3.6.1.4.1.12148.9 | eltekDistributedPlantV7 | ELTEK-DISTRIBUTED-MIB |
| 1.3.6.1.4.1.12148.9.3 | battery | ELTEK-DISTRIBUTED-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.12148.9.3.9 | batteryFloatVoltConfig | ELTEK-DISTRIBUTED-PLANTV4-MIB |