EATON-EPDU-MA-MIB :: outletCurrentUpperWarning

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsEATON-EPDU-MA-MIBoutletCurrentUpperWarning

outletCurrentUpperWarning

Module: EATON-EPDU-MA-MIB

OID (symbolic): EATON-EPDU-MA-MIB::outletCurrentUpperWarning

OID (numeric): 1.3.6.1.4.1.534.6.6.6.1.2.2.1.21

Node type: OBJECT-TYPE

Type: MilliAmps

Access: read-write

Description: The value of the upper warning (non-critical) current threshold for the outlet. This value is reported in milliamps (1/1000th of an amp)

What is outletCurrentUpperWarning?

A settable non-critical high-current threshold (in milliamps) for the outlet; when the outlet's measured current exceeds it, the PDU can raise a warning-level alert before the more severe critical threshold is reached.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.534.6.6.6.1.2.2.1.21
snmpwalk -v2c -c public <target> EATON-EPDU-MA-MIB::outletCurrentUpperWarning

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.534.6.6.6.1.2.2.1.21.1
snmpget -v2c -c public <target> EATON-EPDU-MA-MIB::outletCurrentUpperWarning.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.534.6.6.6.1.2.2.1.21.1 s <value>

Start monitoring Eaton ePDU Managed/Advanced rack power distribution unit with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the EATON-EPDU-MA-MIB::outletCurrentUpperWarning OID value, configure state conditions and alerts, and monitor any Eaton ePDU Managed/Advanced rack power distribution unit from a single console.

OID Breakdown

Upper-level ancestors (9 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.534eatonEATON-OIDS
1.3.6.1.4.1.534.6productsEATON-OIDS
1.3.6.1.4.1.534.6.6pduAgentEATON-OIDS
Numeric OIDNameModule
1.3.6.1.4.1.534.6.6.6eatonEpduMaEATON-EPDU-MA-MIB
1.3.6.1.4.1.534.6.6.6.1boardEATON-EPDU-MA-MIB
1.3.6.1.4.1.534.6.6.6.1.2outletsEATON-EPDU-MA-MIB
1.3.6.1.4.1.534.6.6.6.1.2.2outletTableEATON-EPDU-MA-MIB
1.3.6.1.4.1.534.6.6.6.1.2.2.1outletEntryEATON-EPDU-MA-MIB
1.3.6.1.4.1.534.6.6.6.1.2.2.1.21outletCurrentUpperWarningEATON-EPDU-MA-MIB