All MIBs › DGPUPS-MIB › upsSmartControlSimulatePowerFail
upsSmartControlSimulatePowerFail
Module: DGPUPS-MIB
OID (symbolic): DGPUPS-MIB::upsSmartControlSimulatePowerFail
OID (numeric): 1.3.6.1.4.1.17420.1.1.2.6.2.4
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Setting this variable to simulatePowerFailure(2) causes the UPS switch to battery power.
Setting this value to noSimulatePowerFailure(1) has no effect.
The value noSimulatePowerFailure(1) will always be returned when the variable is read.
What is upsSmartControlSimulatePowerFail?
Writing simulatePowerFailure(2) forces the UPS to switch to battery power as if utility input had actually failed, letting an administrator test failover behavior and runtime without physically disconnecting power; reading the object always returns noSimulatePowerFailure(1). This is useful for periodic UPS testing without waiting for a real outage.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.17420.1.1.2.6.2.4 snmpwalk -v2c -c public <target> DGPUPS-MIB::upsSmartControlSimulatePowerFail
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.17420.1.1.2.6.2.4.1 snmpget -v2c -c public <target> DGPUPS-MIB::upsSmartControlSimulatePowerFail.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.17420.1.1.2.6.2.4.1 i <value>
SNMPv3 example:
snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> upsSmartControlSimulatePowerFail.1
Start monitoring DGP UPS systems with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the DGPUPS-MIB::upsSmartControlSimulatePowerFail OID value, configure state conditions and alerts, and monitor any DGP UPS systems from a single console.
OID Breakdown
Upper-level ancestors (9 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.17420 | dgp | DGPPDU-MIB |
| 1.3.6.1.4.1.17420.1 | products | DGPPDU-MIB |
| 1.3.6.1.4.1.17420.1.1 | hardware | DGPRPM-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.17420.1.1.2 | ups | DGPUPS-MIB |
| 1.3.6.1.4.1.17420.1.1.2.6 | upsControlp | DGPUPS-MIB |
| 1.3.6.1.4.1.17420.1.1.2.6.2 | upsSmartControl | DGPUPS-MIB |
| 1.3.6.1.4.1.17420.1.1.2.6.2.4 | upsSmartControlSimulatePowerFail | DGPUPS-MIB |