All MIBs › DGPUPS-MIB › upsEnvUnderHumidity
upsEnvUnderHumidity
Module: DGPUPS-MIB
OID (symbolic): DGPUPS-MIB::upsEnvUnderHumidity
OID (numeric): 1.3.6.1.4.1.17420.1.1.2.9.2.4
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Alarm dupsAlarmUnderHumidity on when the environment humidity below the value.
What is upsEnvUnderHumidity?
Sets the ambient humidity threshold below which the UPS raises its dupsAlarmUnderHumidity alarm. Administrators configure this to flag conditions where the room has become too dry, which can increase static electricity risk around sensitive electronics.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.17420.1.1.2.9.2.4 snmpwalk -v2c -c public <target> DGPUPS-MIB::upsEnvUnderHumidity
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.17420.1.1.2.9.2.4.1 snmpget -v2c -c public <target> DGPUPS-MIB::upsEnvUnderHumidity.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.17420.1.1.2.9.2.4.1 i <value>
Start monitoring DGP UPS systems with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the DGPUPS-MIB::upsEnvUnderHumidity OID value, configure state conditions and alerts, and monitor any DGP UPS systems from a single console.
OID Breakdown
Upper-level ancestors (9 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.17420 | dgp | DGPPDU-MIB |
| 1.3.6.1.4.1.17420.1 | products | DGPPDU-MIB |
| 1.3.6.1.4.1.17420.1.1 | hardware | DGPRPM-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.17420.1.1.2 | ups | DGPUPS-MIB |
| 1.3.6.1.4.1.17420.1.1.2.9 | upsEnvironment | DGPUPS-MIB |
| 1.3.6.1.4.1.17420.1.1.2.9.2 | upsEnvSetting | DGPUPS-MIB |
| 1.3.6.1.4.1.17420.1.1.2.9.2.4 | upsEnvUnderHumidity | DGPUPS-MIB |