All MIBs › CPS-MIB › upsPhaseInputVoltage
upsPhaseInputVoltage
Module: CPS-MIB
OID (symbolic): CPS-MIB::upsPhaseInputVoltage
OID (numeric): 1.3.6.1.4.1.3808.1.1.1.9.1.2.1.2
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: Getting this OID will return the input voltage that each phase of the UPS can provide. It is represented in 1/10 VAC.
What is upsPhaseInputVoltage?
This read-only integer, obtained by getting this OID, returns the input voltage that a specific phase of the UPS can provide, represented in tenths of a VAC. It reports the incoming voltage measured on one specific phase, letting an admin spot a voltage imbalance across phases on a three-phase feed. For example, an admin compares this reading across all three phase indexes and notices phase 2 reads noticeably lower, indicating an unbalanced feed.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.1.9.1.2.1.2 snmpwalk -v2c -c public <target> CPS-MIB::upsPhaseInputVoltage
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.1.9.1.2.1.2.1 snmpget -v2c -c public <target> CPS-MIB::upsPhaseInputVoltage.1
SNMPv3 example:
snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> upsPhaseInputVoltage.1
Start monitoring UPS product line (vendor unclear, enterprise OID 3808) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS-MIB::upsPhaseInputVoltage OID value, configure state conditions and alerts, and monitor any UPS product line (vendor unclear, enterprise OID 3808) from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.3808 | cps | CPS-MIB |
| 1.3.6.1.4.1.3808.1 | products | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1 | hardware | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.1 | ups | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.1.9 | upsPhase | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.1.9.1 | upsPhaseInput | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.1.9.1.2 | upsPhaseInputTable | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.1.9.1.2.1 | upsPhaseInputEntry | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.1.9.1.2.1.2 | upsPhaseInputVoltage | CPS-MIB |