CPS-MIB :: upsAdvanceControlSimulatePowerFail

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsCPS-MIBupsAdvanceControlSimulatePowerFail

upsAdvanceControlSimulatePowerFail

Module: CPS-MIB

OID (symbolic): CPS-MIB::upsAdvanceControlSimulatePowerFail

OID (numeric): 1.3.6.1.4.1.3808.1.1.1.6.2.4

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: UPS will transfer to backup mode when the variable is set to simulatePowerFailure(2). It is no effective to set this value to noFlashAndBeep(1).

What is upsAdvanceControlSimulatePowerFail?

This read-write enumerated value, when set to simulatePowerFailure, causes the UPS to transfer to backup battery mode even though utility power is actually present. It lets an admin deliberately test how connected equipment and monitoring alerts behave during an outage without waiting for a real one. For example, an admin sets this to simulatePowerFailure(2) during a scheduled DR test to confirm servers correctly detect the transfer to battery and begin their shutdown scripts.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.1.6.2.4
snmpwalk -v2c -c public <target> CPS-MIB::upsAdvanceControlSimulatePowerFail

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.1.6.2.4.1
snmpget -v2c -c public <target> CPS-MIB::upsAdvanceControlSimulatePowerFail.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.3808.1.1.1.6.2.4.1 i <value>

Start monitoring UPS product line (vendor unclear, enterprise OID 3808) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS-MIB::upsAdvanceControlSimulatePowerFail OID value, configure state conditions and alerts, and monitor any UPS product line (vendor unclear, enterprise OID 3808) from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.3808cpsCPS-MIB
1.3.6.1.4.1.3808.1productsCPS-MIB
1.3.6.1.4.1.3808.1.1hardwareCPS-MIB
1.3.6.1.4.1.3808.1.1.1upsCPS-MIB
1.3.6.1.4.1.3808.1.1.1.6upsControlCPS-MIB
1.3.6.1.4.1.3808.1.1.1.6.2upsAdvanceControlCPS-MIB
1.3.6.1.4.1.3808.1.1.1.6.2.4upsAdvanceControlSimulatePowerFailCPS-MIB