CPS-MIB :: upsAdvanceBatteryCapacity

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsCPS-MIBupsAdvanceBatteryCapacity

upsAdvanceBatteryCapacity

Module: CPS-MIB

OID (symbolic): CPS-MIB::upsAdvanceBatteryCapacity

OID (numeric): 1.3.6.1.4.1.3808.1.1.1.2.2.1

Node type: OBJECT-TYPE

Type: Gauge

Access: read-only

Description: The battery capacity expressed in percentage.

What is upsAdvanceBatteryCapacity?

This read-only Gauge reports the battery capacity expressed as a percentage. It is the real-time state-of-charge reading an admin watches to judge how much runtime remains during an outage. For example, an admin sees this drop to 20% during a prolonged outage and initiates a graceful shutdown of dependent servers.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.1.2.2.1
snmpwalk -v2c -c public <target> CPS-MIB::upsAdvanceBatteryCapacity

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.1.2.2.1.1
snmpget -v2c -c public <target> CPS-MIB::upsAdvanceBatteryCapacity.1

Start monitoring UPS product line (vendor unclear, enterprise OID 3808) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS-MIB::upsAdvanceBatteryCapacity OID value, configure state conditions and alerts, and monitor any UPS product line (vendor unclear, enterprise OID 3808) from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.3808cpsCPS-MIB
1.3.6.1.4.1.3808.1productsCPS-MIB
1.3.6.1.4.1.3808.1.1hardwareCPS-MIB
1.3.6.1.4.1.3808.1.1.1upsCPS-MIB
1.3.6.1.4.1.3808.1.1.1.2upsBatteryCPS-MIB
1.3.6.1.4.1.3808.1.1.1.2.2upsAdvanceBatteryCPS-MIB
1.3.6.1.4.1.3808.1.1.1.2.2.1upsAdvanceBatteryCapacityCPS-MIB