All MIBs › CPS-MIB › ePDUOutletConfigMonitoredLowLoadThreshold
ePDUOutletConfigMonitoredLowLoadThreshold
Module: CPS-MIB
OID (symbolic): CPS-MIB::ePDUOutletConfigMonitoredLowLoadThreshold
OID (numeric): 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.4
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in watts. A warning will be issued when the load is less than the threshold value.
A threshold value of 0 effectively disables this warning.
Maximum value must be less than the value returned by the ePDUOutletConfigMonitoredNearOverloadThreshold OID.
0 will be returned if the unit is not Outlet Monitored Rack PDU.
What is ePDUOutletConfigMonitoredLowLoadThreshold?
This read-write integer sets the low-load warning threshold, in watts, for a specific monitored outlet, with 0 disabling the warning, and 0 also returned automatically on units that lack this monitoring capability. Admins use it to detect an individual outlet's equipment going unexpectedly idle, such as a server that has crashed and stopped drawing its normal power. Setting a threshold of 20 watts on an outlet normally drawing 150 watts would trigger a warning if that server's load unexpectedly collapsed to near zero, an early sign of a crash or unplugging.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.4 snmpwalk -v2c -c public <target> CPS-MIB::ePDUOutletConfigMonitoredLowLoadThreshold
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.4.1 snmpget -v2c -c public <target> CPS-MIB::ePDUOutletConfigMonitoredLowLoadThreshold.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.4.1 i <value>
Start monitoring UPS product line (vendor unclear, enterprise OID 3808) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS-MIB::ePDUOutletConfigMonitoredLowLoadThreshold OID value, configure state conditions and alerts, and monitor any UPS product line (vendor unclear, enterprise OID 3808) from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.3808 | cps | CPS-MIB |
| 1.3.6.1.4.1.3808.1 | products | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1 | hardware | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3 | ePDU | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3.3 | ePDUOutlet | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3.3.4 | ePDUOutletConfig | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3.3.4.3 | ePDUOutletConfigMonitoredTable | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3.3.4.3.1 | ePDUOutletConfigMonitoredEntry | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3.3.4.3.1.4 | ePDUOutletConfigMonitoredLowLoadThreshold | CPS-MIB |