All MIBs › CPS-MIB › ePDUOutletBankOverloadRestriction
ePDUOutletBankOverloadRestriction
Module: CPS-MIB
OID (symbolic): CPS-MIB::ePDUOutletBankOverloadRestriction
OID (numeric): 1.3.6.1.4.1.3808.1.1.3.3.6.1.1.2
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: This OID controls the behavior of a Switched Rack PDU bank when an overload condition is possible and additional outlets are requested to be turned on.
Setting this OID to alwaysAllowTurnON (1) will always allow the outlets on the corresponding bank to turn on.
Setting this OID to restrictOnNearOverload (2) will not allow outlets on the corresponding bank to turn on if the ePDULoadBankConfigNearOverloadThreshold OID is exceeded.
Setting this OID to restrictOnOverload (3) will not allow outlets on the corresponding bank to turn on if the ePDULoadBankConfigOverloadThreshold OID is exceeded.
What is ePDUOutletBankOverloadRestriction?
This read-write enumerated integer controls whether outlets on a given bank are allowed to turn on when that bank is near or at overload: alwaysAllowTurnON(1) permits it regardless, restrictOnNearOverload(2) blocks new outlets once the bank's near-overload threshold is exceeded, and restrictOnOverload(3) blocks it only once the bank is fully overloaded. Admins configure this to keep someone from accidentally tripping a bank's breaker by powering on one more device. Setting bank 1 to restrictOnOverload(3) still allows outlets to turn on while the bank is merely near overload, only blocking new power-on attempts once the bank is actually overloaded.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.3.3.6.1.1.2 snmpwalk -v2c -c public <target> CPS-MIB::ePDUOutletBankOverloadRestriction
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.3.3.6.1.1.2.1 snmpget -v2c -c public <target> CPS-MIB::ePDUOutletBankOverloadRestriction.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.3808.1.1.3.3.6.1.1.2.1 i <value>
Start monitoring UPS product line (vendor unclear, enterprise OID 3808) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS-MIB::ePDUOutletBankOverloadRestriction OID value, configure state conditions and alerts, and monitor any UPS product line (vendor unclear, enterprise OID 3808) from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.3808 | cps | CPS-MIB |
| 1.3.6.1.4.1.3808.1 | products | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1 | hardware | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3 | ePDU | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3.3 | ePDUOutlet | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3.3.6 | ePDUOutletBank | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3.3.6.1 | ePDUOutletBankTable | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3.3.6.1.1 | ePDUOutletBankEntry | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.3.3.6.1.1.2 | ePDUOutletBankOverloadRestriction | CPS-MIB |