CPS-MIB :: ePDULoadPhaseConfigOverloadThreshold

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsCPS-MIBePDULoadPhaseConfigOverloadThreshold

ePDULoadPhaseConfigOverloadThreshold

Module: CPS-MIB

OID (symbolic): CPS-MIB::ePDULoadPhaseConfigOverloadThreshold

OID (numeric): 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.4

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value.

Minimum value must be greater than or equal to the value returned by the ePDULoadPhaseConfigNearOverloadThreshold OID.

Maximum value must be less than or equal to the value returned by the ePDULoadDevMaxPhaseLoad OID.

What is ePDULoadPhaseConfigOverloadThreshold?

This read-write integer sets the overload threshold, in amps, at which a phase is considered to have entered an overload condition, and must not exceed the phase's maximum rated load, ePDULoadDevMaxPhaseLoad. Admins configure it to define the actual danger point for that phase rather than relying only on the factory maximum rating. Setting this to 28 amps on a phase rated for a 30 amp maximum builds in a small safety margin before the phase reaches its true physical limit.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.4
snmpwalk -v2c -c public <target> CPS-MIB::ePDULoadPhaseConfigOverloadThreshold

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.4.1
snmpget -v2c -c public <target> CPS-MIB::ePDULoadPhaseConfigOverloadThreshold.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.4.1 i <value>

SNMPv3 example:

snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> ePDULoadPhaseConfigOverloadThreshold.1

Start monitoring UPS product line (vendor unclear, enterprise OID 3808) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS-MIB::ePDULoadPhaseConfigOverloadThreshold OID value, configure state conditions and alerts, and monitor any UPS product line (vendor unclear, enterprise OID 3808) from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.3808cpsCPS-MIB
1.3.6.1.4.1.3808.1productsCPS-MIB
1.3.6.1.4.1.3808.1.1hardwareCPS-MIB
1.3.6.1.4.1.3808.1.1.3ePDUCPS-MIB
1.3.6.1.4.1.3808.1.1.3.2ePDULoadCPS-MIB
1.3.6.1.4.1.3808.1.1.3.2.2ePDULoadPhaseConfigCPS-MIB
1.3.6.1.4.1.3808.1.1.3.2.2.1ePDULoadPhaseConfigTableCPS-MIB
1.3.6.1.4.1.3808.1.1.3.2.2.1.1ePDULoadPhaseConfigEntryCPS-MIB
1.3.6.1.4.1.3808.1.1.3.2.2.1.1.4ePDULoadPhaseConfigOverloadThresholdCPS-MIB