CPS-MIB :: ePDULoadPhaseConfigNearOverloadThreshold

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsCPS-MIBePDULoadPhaseConfigNearOverloadThreshold

ePDULoadPhaseConfigNearOverloadThreshold

Module: CPS-MIB

OID (symbolic): CPS-MIB::ePDULoadPhaseConfigNearOverloadThreshold

OID (numeric): 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.3

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: A threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value.

Minimum value must be greater than the value returned by the ePDULoadPhaseConfigLowLoadThreshold OID.

Maximum value must be less than or equal to the value returned by the ePDULoadPhaseConfigOverloadThreshold OID.

What is ePDULoadPhaseConfigNearOverloadThreshold?

This read-write integer sets the near-overload warning threshold, in amps, for one phase; a warning is issued once the phase's load reaches or exceeds this value, and it must sit between the phase's low-load threshold and its overload threshold. Admins use it as an early-warning trip wire so they can shed load or redistribute equipment before the phase actually overloads. Setting this to 25 amps on a phase whose overload threshold is 30 amps gives the admin a warning buffer to react before that phase actually trips.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.3
snmpwalk -v2c -c public <target> CPS-MIB::ePDULoadPhaseConfigNearOverloadThreshold

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.3.1
snmpget -v2c -c public <target> CPS-MIB::ePDULoadPhaseConfigNearOverloadThreshold.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.3808.1.1.3.2.2.1.1.3.1 i <value>

Start monitoring UPS product line (vendor unclear, enterprise OID 3808) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS-MIB::ePDULoadPhaseConfigNearOverloadThreshold OID value, configure state conditions and alerts, and monitor any UPS product line (vendor unclear, enterprise OID 3808) from a single console.

OID Breakdown

Upper-level ancestors (6 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
Numeric OIDNameModule
1.3.6.1.4.1.3808cpsCPS-MIB
1.3.6.1.4.1.3808.1productsCPS-MIB
1.3.6.1.4.1.3808.1.1hardwareCPS-MIB
1.3.6.1.4.1.3808.1.1.3ePDUCPS-MIB
1.3.6.1.4.1.3808.1.1.3.2ePDULoadCPS-MIB
1.3.6.1.4.1.3808.1.1.3.2.2ePDULoadPhaseConfigCPS-MIB
1.3.6.1.4.1.3808.1.1.3.2.2.1ePDULoadPhaseConfigTableCPS-MIB
1.3.6.1.4.1.3808.1.1.3.2.2.1.1ePDULoadPhaseConfigEntryCPS-MIB
1.3.6.1.4.1.3808.1.1.3.2.2.1.1.3ePDULoadPhaseConfigNearOverloadThresholdCPS-MIB