All MIBs › CPS-MIB › ePDU2GroupTotalPower
ePDU2GroupTotalPower
Module: CPS-MIB
OID (symbolic): CPS-MIB::ePDU2GroupTotalPower
OID (numeric): 1.3.6.1.4.1.3808.1.1.6.8.2
Node type: OBJECT-TYPE
Type: Gauge
Access: read-only
Description: Getting this OID will return the total power consumption of the Rack PDU Daisy Chain group devices in watts. Queries to slave units in an Daisy Chain group will return 0.
What is ePDU2GroupTotalPower?
This read-only gauge reports the combined power consumption, in watts, of all Rack PDU devices in a daisy-chain group, and like the device count it returns 0 when read from a slave unit. It gives an admin a single aggregate power figure for an entire chained PDU group instead of having to sum each unit individually. For example, an admin monitoring a rack fed by four chained PDUs would query the master unit's total power to see the rack's overall draw at a glance.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.6.8.2 snmpwalk -v2c -c public <target> CPS-MIB::ePDU2GroupTotalPower
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.3808.1.1.6.8.2.1 snmpget -v2c -c public <target> CPS-MIB::ePDU2GroupTotalPower.1
Start monitoring UPS product line (vendor unclear, enterprise OID 3808) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPS-MIB::ePDU2GroupTotalPower OID value, configure state conditions and alerts, and monitor any UPS product line (vendor unclear, enterprise OID 3808) from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.3808 | cps | CPS-MIB |
| 1.3.6.1.4.1.3808.1 | products | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1 | hardware | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.6 | ePDU2 | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.6.8 | ePDU2Group | CPS-MIB |
| 1.3.6.1.4.1.3808.1.1.6.8.2 | ePDU2GroupTotalPower | CPS-MIB |