All MIBs › CPQWCRM-MIB › waterCoolUnitSensorValue
waterCoolUnitSensorValue
Module: CPQWCRM-MIB
OID (symbolic): CPQWCRM-MIB::waterCoolUnitSensorValue
OID (numeric): 1.3.6.1.4.1.232.167.2.4.5.2.1.5
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: Value of sensor added to traps, msg index also added (waterCoolUnitMsgIndex)
If msg index = 1, 5 or 6 This value represents the actual Server Intake Temperature.
If msg index = 2: This value represents the bit coded warning condition Bit 0: Top Fan Module Failed Bit 1: Middle Fan Module Failed Bit 2: Bottom Fan Module Failed Bit 3: Top HEX Intake Air Temperature Sensor to Server Failed Bit 4: Top HEX Exhaust Air Temperature Sensor from Server Failed Bit 5: Middle HEX Intake Air Temperature Sensor to Server Failed Bit 6: Middle HEX Exhaust Air Temperature Sensor from Server Failed Bit 7: Bottom HEX Intake Air Temperature Sensor to Server Failed Bit 8: Bottom HEX Exhaust Air Temperature Sensor from Server Failed Bit 9: Air Temperature Sensor Failed Bit 10: Top Fan not installed Bit 11: Middle Fan not installed Bit 12: Bottom Fan not installed Bit 13: Waterflow low Bit 14: Water Unit Temperature Input Out of Range Bit 15: Water Unit Temperature Output Out of Range Bit 16: Waterflow Sensor Value Out of Range Bit 17: Water Valve Failed Bit 18: Leakdetector Failed Bit 19: Heat Load Warning Bit 20: The Condensation Pump has exceeded the max. number of cycles Bit 21: The Condensation Pump has exceeded the max. Running Time
If msg index = 3: This value represents the bit coded alarm condition Bit 0: Leakage Detected Bit 1: Comm. Failure IIC
What is waterCoolUnitSensorValue?
This read-only integer reports the value of an indexed cooling sensor, whose meaning depends on which related alarm message index triggered it, per the MIB's own notes: an intake temperature for message indexes 1, 5, or 6, or a bit-coded warning field (fan and heat-exchanger failures) for message index 2. It gives an admin the actual data behind a fired alarm, which may be a temperature reading or an entirely different bit-coded status depending on context. For example, when tied to message index 2, a returned value with bit 1 set indicates the Middle Fan Module has failed, not a temperature reading at all.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.232.167.2.4.5.2.1.5 snmpwalk -v2c -c public <target> CPQWCRM-MIB::waterCoolUnitSensorValue
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.232.167.2.4.5.2.1.5.1 snmpget -v2c -c public <target> CPQWCRM-MIB::waterCoolUnitSensorValue.1
Start monitoring Legacy Compaq (HP) rack/console environmental-management hardware with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPQWCRM-MIB::waterCoolUnitSensorValue OID value, configure state conditions and alerts, and monitor any Legacy Compaq (HP) rack/console environmental-management hardware from a single console.
OID Breakdown
Upper-level ancestors (7 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.232 | compaq | COMPAQ-ID-REC-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.232.167 | cpqWcrm | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2 | cpqWcrmStatus | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2.4 | cpqWcrmStatusSensorWaterCoolUnit | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2.4.5 | cpqWcrmStatusWaterCoolUnitSensors | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2.4.5.2 | cpqWcrmWaterCoolUnitSensorTable | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2.4.5.2.1 | cpqWcrmWaterCoolUnitSensorEntry | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2.4.5.2.1.5 | waterCoolUnitSensorValue | CPQWCRM-MIB |