CPQWCRM-MIB :: waterCoolUnitSensorType

MIB Reference — IPNetwork Monitor · Updated September 14, 2026

All MIBsCPQWCRM-MIBwaterCoolUnitSensorType

waterCoolUnitSensorType

Module: CPQWCRM-MIB

OID (symbolic): CPQWCRM-MIB::waterCoolUnitSensorType

OID (numeric): 1.3.6.1.4.1.232.167.2.4.5.2.1.2

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: Type of sensor which is connected to internal sensor to sensor[internalSensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: average temperature of air inlet to rack, average or max/min from each HEX 5: average temperature of air outlet from rack, average or max/min from each HEX 6: heatflow sensor 7: alarm: Bit 0: Leakage Bit 1: IIC Failure 8: warning: Bit 0..2: Fan Tach 1..3 Bit 3,4: Temp. sensor HEX1 In,Out Bit 5,6: Temp. sensor HEX2 In,Out Bit 7,8: Temp. sensor HEX3 In,Out Bit 9: Air temp. sensor Bit 10..12: IIC failure, HEX1..3 Bit 13: Waterflow low Bit 14,15: Watertemp. In,Out Bit 16: Waterflow sensor fail. Bit 17: Magnetic valve fail. Bit 18: Leakdetector fail. Bit 19: Uneven heat load Bit 20: Condensation Pump Cycles > Max Bit 21: Condensation Pump Running Time > Max 9: rpm speed of Fan1 10: rpm speed of Fan2 11: rpm speed of Fan3 12: fanSpeed setpoint, calculated from average temperatures 13: temperature air inlet to rack, HEX 1 14: temperature air outlet from rack, HEX 1 15: temperature air inlet to rack, HEX 1 16: temperature air outlet from rack, HEX 1 17: temperature air inlet to rack, HEX 1 18: temperature air outlet from rack, HEX 1 19: water temperature In 20: water temperature Out 21: water Flow 22: water valve status: MCS:0: Valve opened, 1: valve closed; MCSS: valve setpoint (%) 23: status: Bit 0..Bit 2: fan module 1..3 available Bit 3: water module available 24: condensation pump number of seconds on counter (last operating time) 25: condensation pump on/off cycle counter 26: rpm speed of Fan4 27: rpm speed of Fan5 28: rpm speed of Fan6 29: status of transfer switch, 1=AC1, 2=AC2, 3=AC1 and AC2 30: water valve actual value (%)

What is waterCoolUnitSensorType?

This read-only enumerated value reports what a given index in the water-cooling unit's sensor table actually measures, such as air-inlet temperature, air-outlet temperature, heat flow, or a bit-coded alarm or warning condition. It tells an admin exactly what physical measurement a specific index represents before interpreting its value. For example, a type value of 5 (tempOut) on an index means that sensor reports the average air temperature leaving the rack through the heat exchanger.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.232.167.2.4.5.2.1.2
snmpwalk -v2c -c public <target> CPQWCRM-MIB::waterCoolUnitSensorType

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.232.167.2.4.5.2.1.2.1
snmpget -v2c -c public <target> CPQWCRM-MIB::waterCoolUnitSensorType.1

Start monitoring Legacy Compaq (HP) rack/console environmental-management hardware with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPQWCRM-MIB::waterCoolUnitSensorType OID value, configure state conditions and alerts, and monitor any Legacy Compaq (HP) rack/console environmental-management hardware from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.232compaqCOMPAQ-ID-REC-MIB
Numeric OIDNameModule
1.3.6.1.4.1.232.167cpqWcrmCPQWCRM-MIB
1.3.6.1.4.1.232.167.2cpqWcrmStatusCPQWCRM-MIB
1.3.6.1.4.1.232.167.2.4cpqWcrmStatusSensorWaterCoolUnitCPQWCRM-MIB
1.3.6.1.4.1.232.167.2.4.5cpqWcrmStatusWaterCoolUnitSensorsCPQWCRM-MIB
1.3.6.1.4.1.232.167.2.4.5.2cpqWcrmWaterCoolUnitSensorTableCPQWCRM-MIB
1.3.6.1.4.1.232.167.2.4.5.2.1cpqWcrmWaterCoolUnitSensorEntryCPQWCRM-MIB
1.3.6.1.4.1.232.167.2.4.5.2.1.2waterCoolUnitSensorTypeCPQWCRM-MIB