All MIBs › CPQWCRM-MIB › internalSensorType
internalSensorType
Module: CPQWCRM-MIB
OID (symbolic): CPQWCRM-MIB::internalSensorType
OID (numeric): 1.3.6.1.4.1.232.167.2.3.5.2.1.2
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-only
Description: Type of sensor which is connected to internal sensor to sensor[internalSensorIndex] 1: no sensor connected 2: sensor failure 3: value overflow 4: sensor type 1, access sensor 5: sensor type 2, vibration sensor 6: sensor type 3, motion sensor 7: sensor type 4, smoke sensor 8: sensor type 5, air flow sensor 9: sensor type 6, reserved 10: sensor type 7, temperature sensor 11: sensor type 8, 4..20mA sensor 12: sensor type 9, humidity sensor 13: user sensor with normally opened contact 14: user sensor with normally closed contact 15: door locked sensor from locking device 16: remote unlock sensor (e.g. external keypad) 17: voltage sensor, indicates status of main voltage (OK, NOK) 18: voltage value 19: fan status, from Environmental Controller-FAS-Unit 20: leakage sensor
What is internalSensorType?
This read-only enumerated value reports what kind of physical sensor is wired into a given internalSensorIndex slot on port 1's unit, such as access, vibration, motion, smoke, or air-flow sensors. It tells an admin exactly what physical event a subsequent status change or alarm actually represents. For example, a type value of 6 (motion) on index 3 means an alarm from that slot indicates physical movement was detected near the rack, not a temperature or access issue.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.232.167.2.3.5.2.1.2 snmpwalk -v2c -c public <target> CPQWCRM-MIB::internalSensorType
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.232.167.2.3.5.2.1.2.1 snmpget -v2c -c public <target> CPQWCRM-MIB::internalSensorType.1
Start monitoring Legacy Compaq (HP) rack/console environmental-management hardware with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPQWCRM-MIB::internalSensorType OID value, configure state conditions and alerts, and monitor any Legacy Compaq (HP) rack/console environmental-management hardware from a single console.
OID Breakdown
Upper-level ancestors (7 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.232 | compaq | COMPAQ-ID-REC-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.232.167 | cpqWcrm | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2 | cpqWcrmStatus | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2.3 | cpqWcrmStatusSensorInternal | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2.3.5 | cpqWcrmStatusInternalSensors | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2.3.5.2 | cpqWcrmInternalSensorTable | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2.3.5.2.1 | cpqWcrmInternalSensorEntry | CPQWCRM-MIB |
| 1.3.6.1.4.1.232.167.2.3.5.2.1.2 | internalSensorType | CPQWCRM-MIB |