Module: CPQPOWER-MIB

OID (symbolic): CPQPOWER-MIB::upsInputLineBads

OID (numeric): 1.3.6.1.4.1.232.165.3.3.2

Node type: OBJECT-TYPE

Type: Counter

Access: read-only

Description: The number of times the Input was out of tolerance in voltage or frequency.

What is upsInputLineBads?

This is a running counter of how many times the incoming utility power was detected out of tolerance in voltage or frequency. A rising count over time signals a noisy or unstable utility feed even if the UPS successfully compensated each time. For example, if upsInputLineBads jumps by dozens of events overnight, facilities staff might investigate whether a nearby piece of equipment is causing line disturbances.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.232.165.3.3.2
snmpwalk -v2c -c public <target> CPQPOWER-MIB::upsInputLineBads

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.232.165.3.3.2.1
snmpget -v2c -c public <target> CPQPOWER-MIB::upsInputLineBads.1

Start monitoring Compaq/HP-managed UPS/PDU power infrastructure with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CPQPOWER-MIB::upsInputLineBads OID value, configure state conditions and alerts, and monitor any Compaq/HP-managed UPS/PDU power infrastructure from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.232compaqCOMPAQ-ID-REC-MIB
Numeric OIDNameModule
1.3.6.1.4.1.232.165cpqPowerCPQPOWER-MIB
1.3.6.1.4.1.232.165.3upsCPQPOWER-MIB
1.3.6.1.4.1.232.165.3.3upsInputCPQPOWER-MIB
1.3.6.1.4.1.232.165.3.3.2upsInputLineBadsCPQPOWER-MIB