All MIBs › CCPOWER-MIB › disconnect1Temperature
disconnect1Temperature
Module: CCPOWER-MIB
OID (symbolic): CCPOWER-MIB::disconnect1Temperature
OID (numeric): 1.3.6.1.4.1.18642.1.1.1.6
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: Temperature which when exceeded will cause a specific load to disconnect. Return value is XX representing XX ?C.
What is disconnect1Temperature?
This sets the temperature threshold that, once crossed, disconnects load bank 1, independent of the battery-voltage disconnect for that same bank, per the description. Having a separate thermal trip for bank 1 means the plant can shed that load purely for heat protection - for example a cabinet cooling-fan failure - even while disconnect1Voltage shows the battery voltage itself is still healthy. A setting of 50 (50 degrees C) would drop load bank 1 if the monitored cabinet temperature reaches 50 degrees C, regardless of how much charge remains in the batteries.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.18642.1.1.1.6 snmpwalk -v2c -c public <target> CCPOWER-MIB::disconnect1Temperature
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.18642.1.1.1.6.1 snmpget -v2c -c public <target> CCPOWER-MIB::disconnect1Temperature.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.18642.1.1.1.6.1 i <value>
Start monitoring DC rectifier/power-plant equipment (enterprise OID 18642) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the CCPOWER-MIB::disconnect1Temperature OID value, configure state conditions and alerts, and monitor any DC rectifier/power-plant equipment (enterprise OID 18642) from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.18642 | ccpower | CCPOWER-MIB |
| 1.3.6.1.4.1.18642.1 | dcSystem | CCPOWER-MIB |
| 1.3.6.1.4.1.18642.1.1 | readWriteObjects | CCPOWER-MIB |
| 1.3.6.1.4.1.18642.1.1.1 | settings | CCPOWER-MIB |
| 1.3.6.1.4.1.18642.1.1.1.6 | disconnect1Temperature | CCPOWER-MIB |