All MIBs › USHA-MIB › upsBatteryTest
upsBatteryTest
Module: USHA-MIB
OID (symbolic): USHA-MIB::upsBatteryTest
OID (numeric): 1.3.6.1.4.1.2468.1.2.1.1.6.2
Node type: OBJECT-TYPE
Type: INTEGER
Access: read-write
Description: This object specify the battery test type and initiate battery test. If battTestWithTime selected, the test time is refer to upsTestBatteryTestTime.
What is upsBatteryTest?
Write this to start a battery self-test: a quick 10-second test, a test that runs until the battery reaches low, a test for the duration set in upsTestBatteryTestSettingTime, a cancel of an in-progress test, or a clear of stored test info - the main control an admin uses to verify battery health on demand.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.2468.1.2.1.1.6.2 snmpwalk -v2c -c public <target> USHA-MIB::upsBatteryTest
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.2468.1.2.1.1.6.2.1 snmpget -v2c -c public <target> USHA-MIB::upsBatteryTest.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.2468.1.2.1.1.6.2.1 i <value>
Start monitoring Ingrasys / USHA-branded Uninterruptible Power Supply (UPS) units (battery health/power-state trap status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the USHA-MIB::upsBatteryTest OID value, configure state conditions and alerts, and monitor any Ingrasys / USHA-branded Uninterruptible Power Supply (UPS) units (battery health/power-state trap status) from a single console.
OID Breakdown
Upper-level ancestors (6 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.2468 | ingrasys | USHA-MIB |
| 1.3.6.1.4.1.2468.1 | product | USHA-MIB |
| 1.3.6.1.4.1.2468.1.2 | upsAgent | USHA-MIB |
| 1.3.6.1.4.1.2468.1.2.1 | ushap | USHA-MIB |
| 1.3.6.1.4.1.2468.1.2.1.1 | upsObjectGroup | USHA-MIB |
| 1.3.6.1.4.1.2468.1.2.1.1.6 | upsTestGroup | USHA-MIB |
| 1.3.6.1.4.1.2468.1.2.1.1.6.2 | upsBatteryTest | USHA-MIB |