Sentry4-MIB :: st4InputCordActivePowerHysteresis

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › Sentry4-MIB › st4InputCordActivePowerHysteresis

st4InputCordActivePowerHysteresis

Module: Sentry4-MIB

OID (symbolic): Sentry4-MIB::st4InputCordActivePowerHysteresis

OID (numeric): 1.3.6.1.4.1.1718.4.1.3.1.1

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description: The active power hysteresis of the input cord in Watts.

What is st4InputCordActivePowerHysteresis?

Read-write deadband, in Watts, that active power must move back past before an alarm/warning state on the cord's active power is allowed to clear or re-trigger. Admins raise this above the default to stop a load hovering right at a threshold from generating repeated flapping alarms.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.1718.4.1.3.1.1
snmpwalk -v2c -c public <target> Sentry4-MIB::st4InputCordActivePowerHysteresis

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.1718.4.1.3.1.1.1
snmpget -v2c -c public <target> Sentry4-MIB::st4InputCordActivePowerHysteresis.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.1718.4.1.3.1.1.1 i <value>

Start monitoring Server Technology Sentry4 PRO1/PRO2 series Smart/Switched CDU and PDU (per-line/phase power/status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the Sentry4-MIB::st4InputCordActivePowerHysteresis OID value, configure state conditions and alerts, and monitor any Server Technology Sentry4 PRO1/PRO2 series Smart/Switched CDU and PDU (per-line/phase power/status) from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.1718serverTechSentry3-MIB
Numeric OIDNameModule
1.3.6.1.4.1.1718.4sentry4Sentry4-MIB
1.3.6.1.4.1.1718.4.1st4ObjectsSentry4-MIB
1.3.6.1.4.1.1718.4.1.3st4InputCordsSentry4-MIB
1.3.6.1.4.1.1718.4.1.3.1st4InputCordCommonConfigSentry4-MIB
1.3.6.1.4.1.1718.4.1.3.1.1st4InputCordActivePowerHysteresisSentry4-MIB