SL81-STD-MIB :: esPointValueInt

MIB Reference — IPNetwork Monitor · Updated September 23, 2026

All MIBs › SL81-STD-MIB › esPointValueInt

esPointValueInt

Module: SL81-STD-MIB

OID (symbolic): SL81-STD-MIB::esPointValueInt

OID (numeric): 1.3.6.1.4.1.3052.5.1.1.1.1.6

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: A number referring to the value of a point on an EventSensor.

If the point class is temperature, then this object is the temperature in its configured scale (default is Fahrenheit).

If the point class is contact closure or relay, then this object is either 0 (open) or 1 (closed).

If the point class is humidity, then this object is the percent relative humidity.

If the point class is analog input, then this object is the signed input value in tenths of the configured units.

For any point class except relay, this object is read-only.

For relays, setting this object to 1 closes the relay, while setting it to 0 opens it. Setting it to any value greater than 1 closes the relay for that many seconds (up to 3600), after which time it opens the relay. This works regardless of the control mode of the relay.

What is esPointValueInt?

The current reading of this monitored point as a signed integer, whose meaning depends on point class: degrees for temperature, 0/1 (open/closed) for contact closures and relays, percent for humidity, or tenths of the configured unit for analog inputs. For relays only, writing a value greater than 0 closes the relay (indefinitely if 1, or temporarily up to 3600 seconds for higher values).

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.3052.5.1.1.1.1.6
snmpwalk -v2c -c public <target> SL81-STD-MIB::esPointValueInt

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.3052.5.1.1.1.1.6.1
snmpget -v2c -c public <target> SL81-STD-MIB::esPointValueInt.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.3052.5.1.1.1.1.6.1 i <value>

Start monitoring Asentria SL81-series remote site monitoring device (environmental sensor point/alarm status) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the SL81-STD-MIB::esPointValueInt OID value, configure state conditions and alerts, and monitor any Asentria SL81-series remote site monitoring device (environmental sensor point/alarm status) from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.3052asentriaASENTRIA-ROOT-MIB
Numeric OIDNameModule
1.3.6.1.4.1.3052.5sl81SL81-STD-MIB
1.3.6.1.4.1.3052.5.1statusSL81-STD-MIB
1.3.6.1.4.1.3052.5.1.1eventSensorStatusSL81-STD-MIB
1.3.6.1.4.1.3052.5.1.1.1esPointTableSL81-STD-MIB
1.3.6.1.4.1.3052.5.1.1.1.1esPointEntrySL81-STD-MIB
1.3.6.1.4.1.3052.5.1.1.1.1.6esPointValueIntSL81-STD-MIB