Description: Actual message status 1: not available 2: configuration has changed (sensor new, changed, lost) 3: error 4: OK 5: alarm, e.g. smoke, vibration... 6: warning of analog value, value reached high warning threshold 7: analog value too low, value reached low threshold (Alarm) 8: analog value too high, value reached high threshold (Alarm) 9: warning of analog value, value reached low warning threshold 10: output is set to OFF 11: output is set to ON 12: door is open 13: door is closed 14: door is locked 15: door is unlocked by remote input, e.g. external card reader 16: door is unlocked by reader or keypad connected 17: door is unlocked by SNMP set command 18: door is unlocked by WEB 19: door is unlocked by timer 20: no access, wrong key code or card number 21: lost 22: detected 23: battery low, wireless sensor 24: sensor cable broken 25: sensor cable short 26: sensor calibration in progress 27: sensor is inactive 28: sensor is active 29: no Power (PSM) 30: read only (SD, USB-Stick) 31: control boards of LCP exchanged.
What is cmcIIIMsgStatus?
This message's actual status, from a large enumeration covering conditions like alarm (smoke, vibration), high/low warning or alarm thresholds, door open/closed/locked, sensor lost/detected, battery low, cable broken or shorted, or output set on/off. This is the specific condition behind the message text, and feeds the alarmSensorDevice/alarmDevice trap notifications.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.2606.7.4.3.2.1.4 snmpwalk -v2c -c public <target> RITTAL-CMC-III-MIB::cmcIIIMsgStatus
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.2606.7.4.3.2.1.4.1 snmpget -v2c -c public <target> RITTAL-CMC-III-MIB::cmcIIIMsgStatus.1
Start monitoring Rittal CMC III unit, data center rack/enclosure monitoring system (temperature/humidity/power sensors) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the RITTAL-CMC-III-MIB::cmcIIIMsgStatus OID value, configure state conditions and alerts, and monitor any Rittal CMC III unit, data center rack/enclosure monitoring system (temperature/humidity/power sensors) from a single console.
OID Breakdown
Upper-level ancestors (7 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.2606 | rittal | RITTAL-CMC-TC-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.2606.7 | cmcIII | RITTAL-CMC-III-MIB |
| 1.3.6.1.4.1.2606.7.4 | cmcIIIDevice | RITTAL-CMC-III-MIB |
| 1.3.6.1.4.1.2606.7.4.3 | cmcIIIMsgs | RITTAL-CMC-III-MIB |
| 1.3.6.1.4.1.2606.7.4.3.2 | cmcIIIMsgTable | RITTAL-CMC-III-MIB |
| 1.3.6.1.4.1.2606.7.4.3.2.1 | cmcIIIMsgEntry | RITTAL-CMC-III-MIB |