RITTAL-CMC-III-MIB :: cmcIIILogicRelay

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › RITTAL-CMC-III-MIB › cmcIIILogicRelay

cmcIIILogicRelay

Module: RITTAL-CMC-III-MIB

OID (symbolic): RITTAL-CMC-III-MIB::cmcIIILogicRelay

OID (numeric): 1.3.6.1.4.1.2606.7.3.2.4

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: Logic of alarm relay: (1) Relay will pick up in case of an alarm (2) Relay will release in case of an alarm (3) Relay disabled.

What is cmcIIILogicRelay?

The alarm relay's switching logic: closeAtAlarm(1, the default, relay picks up on alarm), openAtAlarm(2, relay releases on alarm), or disabled(3). Admins choose openAtAlarm for a fail-safe wiring where losing power to the CMC-III itself also triggers the external alarm circuit.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.2606.7.3.2.4
snmpwalk -v2c -c public <target> RITTAL-CMC-III-MIB::cmcIIILogicRelay

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.2606.7.3.2.4.1
snmpget -v2c -c public <target> RITTAL-CMC-III-MIB::cmcIIILogicRelay.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.2606.7.3.2.4.1 i <value>

Start monitoring Rittal CMC III unit, data center rack/enclosure monitoring system (temperature/humidity/power sensors) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the RITTAL-CMC-III-MIB::cmcIIILogicRelay OID value, configure state conditions and alerts, and monitor any Rittal CMC III unit, data center rack/enclosure monitoring system (temperature/humidity/power sensors) from a single console.

OID Breakdown

Upper-level ancestors (7 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.2606rittalRITTAL-CMC-TC-MIB
Numeric OIDNameModule
1.3.6.1.4.1.2606.7cmcIIIRITTAL-CMC-III-MIB
1.3.6.1.4.1.2606.7.3cmcIIISetupRITTAL-CMC-III-MIB
1.3.6.1.4.1.2606.7.3.2cmcIIISetupGeneralRITTAL-CMC-III-MIB
1.3.6.1.4.1.2606.7.3.2.4cmcIIILogicRelayRITTAL-CMC-III-MIB