RARITAN-PX2-PDU2-MIB :: unitSensorResetValue

MIB Reference — IPNetwork Monitor

All MIBsRARITAN-PX2-PDU2-MIBunitSensorResetValue

unitSensorResetValue

Module: RARITAN-PX2-PDU2-MIB

OID (symbolic): RARITAN-PX2-PDU2-MIB::unitSensorResetValue

OID (numeric): 1.3.6.1.4.1.13742.6.4.8.1.1.1

Node type: OBJECT-TYPE

Type: Integer32

Access: read-write

Description:

Writing to this variable sets a new value for the addressed sensor. Only accumulating sensors (e.g. energy counters) can be reset, and currently the only supported value is 0. Writing any other value returns an error. This variable will always read as 0. This object applies only to multi-inlet PDUs.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.13742.6.4.8.1.1.1
snmpwalk -v2c -c public <target> RARITAN-PX2-PDU2-MIB::unitSensorResetValue

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.13742.6.4.8.1.1.1.1
snmpget -v2c -c public <target> RARITAN-PX2-PDU2-MIB::unitSensorResetValue.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.13742.6.4.8.1.1.1.1 i <value>

OID Breakdown

Numeric OIDNameModule
1isoLANART-AGENT
1.3orgBIANCA-BRICK-PPP-MIB
1.3.6dodBIANCA-BRICK-PPP-MIB
1.3.6.1internetBIANCA-BRICK-PPP-MIB
1.3.6.1.4privateBIANCA-BRICK-PPP-MIB
1.3.6.1.4.1enterprisesANIROOT-MIB
1.3.6.1.4.1.13742raritanRARITAN-PX2-PDU2-MIB
1.3.6.1.4.1.13742.6pdu2RARITAN-PX2-PDU2-MIB
1.3.6.1.4.1.13742.6.4controlRARITAN-PX2-PDU2-MIB
1.3.6.1.4.1.13742.6.4.8unitSensorControlRARITAN-PX2-PDU2-MIB
1.3.6.1.4.1.13742.6.4.8.1unitSensorControlTableRARITAN-PX2-PDU2-MIB
1.3.6.1.4.1.13742.6.4.8.1.1unitSensorControlEntryRARITAN-PX2-PDU2-MIB
1.3.6.1.4.1.13742.6.4.8.1.1.1unitSensorResetValueRARITAN-PX2-PDU2-MIB