All MIBs › LIEBERT-GP-POWER-MIB › lgpPwrTransferToBypass
lgpPwrTransferToBypass
Module: LIEBERT-GP-POWER-MIB
OID (symbolic): LIEBERT-GP-POWER-MIB::lgpPwrTransferToBypass
OID (numeric): 1.3.6.1.4.1.476.1.42.3.5.6.6
Node type: OBJECT-TYPE
Type: Integer32
Access: read-write
Description: Transfer to Bypass Command. This command will initiate a transfer of the load to the bypass of the system. This command should be sent with a parameter of 1. This variable doesn't return a value when read.
What is lgpPwrTransferToBypass?
A command object, sent with a value of 1, that initiates a transfer of the critical load onto the bypass source. Admins use this to intentionally move load off the inverter, for example ahead of scheduled UPS maintenance.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.6.6 snmpwalk -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrTransferToBypass
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.6.6.1 snmpget -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrTransferToBypass.1
Set instance 1 (SNMPv2c):
snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.5.6.6.1 i <value>
Start monitoring Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-POWER-MIB::lgpPwrTransferToBypass OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.5 | lgpPower | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.5.6 | lgpPwrControl | LIEBERT-GP-POWER-MIB |
| 1.3.6.1.4.1.476.1.42.3.5.6.6 | lgpPwrTransferToBypass | LIEBERT-GP-POWER-MIB |