LIEBERT-GP-POWER-MIB :: lgpPwrStateOutputSource

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-POWER-MIB › lgpPwrStateOutputSource

lgpPwrStateOutputSource

Module: LIEBERT-GP-POWER-MIB

OID (symbolic): LIEBERT-GP-POWER-MIB::lgpPwrStateOutputSource

OID (numeric): 1.3.6.1.4.1.476.1.42.3.5.3.31

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: The UPS's output power source (inverter, bypass, or none). NOTE: It is possible that the load still has power from the Maintenance Bypass.

What is lgpPwrStateOutputSource?

Reports the UPS's actual output power source: none, inverter, bypass, or maintenanceBypass. The MIB notes the load may still have power from Maintenance Bypass even when this doesn't say so directly, so it should be read alongside the maintenance breaker state points.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.3.31
snmpwalk -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrStateOutputSource

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.3.31.1
snmpget -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrStateOutputSource.1

Start monitoring Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-POWER-MIB::lgpPwrStateOutputSource OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.5lgpPowerLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.5.3lgpPwrStatusLIEBERT-GP-POWER-MIB
1.3.6.1.4.1.476.1.42.3.5.3.31lgpPwrStateOutputSourceLIEBERT-GP-POWER-MIB