LIEBERT-GP-POWER-MIB :: lgpPwrPhaseDifferenceLimit

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-POWER-MIB › lgpPwrPhaseDifferenceLimit

lgpPwrPhaseDifferenceLimit

Module: LIEBERT-GP-POWER-MIB

OID (symbolic): LIEBERT-GP-POWER-MIB::lgpPwrPhaseDifferenceLimit

OID (numeric): 1.3.6.1.4.1.476.1.42.3.5.4.5

Node type: OBJECT-TYPE

Type: Integer32

Access: read-only

Description: The maximum phase difference (between the well known input sources ) in which a transfer to an available input source is permitted.

What is lgpPwrPhaseDifferenceLimit?

The maximum phase difference, in units of 0.1 degrees, allowed between the well-known input sources for a transfer between them to be permitted. This is the configured safety threshold that lgpPwrSyncPhaseAngle is checked against before the system allows a source transfer.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.4.5
snmpwalk -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrPhaseDifferenceLimit

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.4.5.1
snmpget -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrPhaseDifferenceLimit.1

Start monitoring Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-POWER-MIB::lgpPwrPhaseDifferenceLimit OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.5lgpPowerLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.5.4lgpPwrSettingsLIEBERT-GP-POWER-MIB
1.3.6.1.4.1.476.1.42.3.5.4.5lgpPwrPhaseDifferenceLimitLIEBERT-GP-POWER-MIB