LIEBERT-GP-POWER-MIB :: lgpPwrOutputToLoadOnBypass

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-POWER-MIB › lgpPwrOutputToLoadOnBypass

lgpPwrOutputToLoadOnBypass

Module: LIEBERT-GP-POWER-MIB

OID (symbolic): LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoadOnBypass

OID (numeric): 1.3.6.1.4.1.476.1.42.3.5.3.10

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-only

Description: The present source of output power is the Bypass.

What is lgpPwrOutputToLoadOnBypass?

Reports whether the present source of output power to the load is the bypass (yes/no). This is the complementary check to lgpPwrOutputToLoadOnInverter, confirming when the load is running unprotected (or semi-protected) through bypass instead of the inverter.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.3.10
snmpwalk -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoadOnBypass

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.3.10.1
snmpget -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoadOnBypass.1

Start monitoring Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-POWER-MIB::lgpPwrOutputToLoadOnBypass OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.5lgpPowerLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.5.3lgpPwrStatusLIEBERT-GP-POWER-MIB
1.3.6.1.4.1.476.1.42.3.5.3.10lgpPwrOutputToLoadOnBypassLIEBERT-GP-POWER-MIB