All MIBs › LIEBERT-GP-POWER-MIB › lgpPwrLoadOnSource
lgpPwrLoadOnSource
Module: LIEBERT-GP-POWER-MIB
OID (symbolic): LIEBERT-GP-POWER-MIB::lgpPwrLoadOnSource
OID (numeric): 1.3.6.1.4.1.476.1.42.3.5.4.2
Node type: OBJECT-TYPE
Type: OBJECT IDENTIFIER
Access: read-only
Description: The well known measurement source from the 'lgpPwrWellKnownMeasurements' sub-tree that is currently powering the output (load).
What is lgpPwrLoadOnSource?
The well-known measurement source OID identifying which input source is presently powering the output load. Comparing this to lgpPwrPreferredSource tells an admin whether the system is currently running on its preferred source or has failed over to an alternate one.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.4.2 snmpwalk -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrLoadOnSource
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.4.2.1 snmpget -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrLoadOnSource.1
SNMPv3 example:
snmpget -v3 -l authPriv -u snmpv3-user -a SHA -A "AuthPassword1" -x AES -X "PrivPassword1" <target> lgpPwrLoadOnSource.1
Start monitoring Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-POWER-MIB::lgpPwrLoadOnSource OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.5 | lgpPower | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.5.4 | lgpPwrSettings | LIEBERT-GP-POWER-MIB |
| 1.3.6.1.4.1.476.1.42.3.5.4.2 | lgpPwrLoadOnSource | LIEBERT-GP-POWER-MIB |