LIEBERT-GP-POWER-MIB :: lgpPwrLoadCircuitState

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-POWER-MIB › lgpPwrLoadCircuitState

lgpPwrLoadCircuitState

Module: LIEBERT-GP-POWER-MIB

OID (symbolic): LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuitState

OID (numeric): 1.3.6.1.4.1.476.1.42.3.5.6.2.1.4

Node type: OBJECT-TYPE

Type: INTEGER

Access: read-write

Description: This identifier indicates the state of the load circuit. When read, only a closed or open response will be returned. When written to, the state of the circuit will transition to desired state.

What is lgpPwrLoadCircuitState?

Reports and controls whether a given switchable load circuit is on, off, or at its default state; reads only return on or off, but a write can command a transition. This is how an admin remotely powers a specific outlet bank down for a rolling reboot or maintenance without cutting the whole UPS output.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.6.2.1.4
snmpwalk -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuitState

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.6.2.1.4.1
snmpget -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuitState.1

Set instance 1 (SNMPv2c):

snmpset -v2c -c private <target> 1.3.6.1.4.1.476.1.42.3.5.6.2.1.4.1 i <value>

Start monitoring Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-POWER-MIB::lgpPwrLoadCircuitState OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.5lgpPowerLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.5.6lgpPwrControlLIEBERT-GP-POWER-MIB
1.3.6.1.4.1.476.1.42.3.5.6.2lgpPwrLoadCircuitTableLIEBERT-GP-POWER-MIB
1.3.6.1.4.1.476.1.42.3.5.6.2.1lgpPwrLoadCircuitEntryLIEBERT-GP-POWER-MIB
1.3.6.1.4.1.476.1.42.3.5.6.2.1.4lgpPwrLoadCircuitStateLIEBERT-GP-POWER-MIB