All MIBs › LIEBERT-GP-POWER-MIB › lgpPwrLineMeasurementVoltsLN
lgpPwrLineMeasurementVoltsLN
Module: LIEBERT-GP-POWER-MIB
OID (symbolic): LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLN
OID (numeric): 1.3.6.1.4.1.476.1.42.3.5.2.3.1.5
Node type: OBJECT-TYPE
Type: Integer32
Access: read-only
Description: The present Line-to-neutral voltage measurement for the indicated source. The line being measured is given by the lgpPwrLineMeasurementIndex where [1 = A, 2 = B, 3 = C].
What is lgpPwrLineMeasurementVoltsLN?
The present line-to-neutral voltage for one line (A, B, or C, per lgpPwrLineMeasurementIndex) of a given measurement point, in Volts. This lets an admin spot phase imbalance on wye-configured systems that a single combined voltage reading wouldn't reveal.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.2.3.1.5 snmpwalk -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLN
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.2.3.1.5.1 snmpget -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLN.1
Start monitoring Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-POWER-MIB::lgpPwrLineMeasurementVoltsLN OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.5 | lgpPower | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.5.2 | lgpPwrMeasurements | LIEBERT-GP-POWER-MIB |
| 1.3.6.1.4.1.476.1.42.3.5.2.3 | lgpPwrLineMeasurementTable | LIEBERT-GP-POWER-MIB |
| 1.3.6.1.4.1.476.1.42.3.5.2.3.1 | lgpPwrLineMeasurementEntry | LIEBERT-GP-POWER-MIB |
| 1.3.6.1.4.1.476.1.42.3.5.2.3.1.5 | lgpPwrLineMeasurementVoltsLN | LIEBERT-GP-POWER-MIB |