All MIBs › LIEBERT-GP-POWER-MIB › lgpPwrInverterOverloadShutdownTime
lgpPwrInverterOverloadShutdownTime
Module: LIEBERT-GP-POWER-MIB
OID (symbolic): LIEBERT-GP-POWER-MIB::lgpPwrInverterOverloadShutdownTime
OID (numeric): 1.3.6.1.4.1.476.1.42.3.5.3.30
Node type: OBJECT-TYPE
Type: Integer32
Access: read-only
Description: The calculated time remaining before inverter shutdown. The calculated time of inverter operation remaining for the present overload event.
Note: If the inverter is not experiencing an overload event this point will return 65535 indicating this value is unavailable.
What is lgpPwrInverterOverloadShutdownTime?
The calculated time remaining, in seconds, of inverter operation for the present overload event; the MIB notes it returns 65535 when the inverter isn't currently overloaded (meaning the value should be disregarded). This is the countdown an admin watches to shed load before the inverter shuts itself down to protect its hardware.
Examples
Walk all instances (SNMPv2c):
snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.3.30 snmpwalk -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrInverterOverloadShutdownTime
Get a specific instance (index 1):
snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.3.30.1 snmpget -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrInverterOverloadShutdownTime.1
Start monitoring Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-POWER-MIB::lgpPwrInverterOverloadShutdownTime OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) from a single console.
OID Breakdown
Upper-level ancestors (11 from the standard OID tree / other modules)
| Numeric OID | Name | Module |
|---|---|---|
| 1 | iso | LANART-AGENT |
| 1.3 | org | AirPair-MIB |
| 1.3.6 | dod | AirPair-MIB |
| 1.3.6.1 | internet | AirPair-MIB |
| 1.3.6.1.4 | private | AirPair-MIB |
| 1.3.6.1.4.1 | enterprises | AirPair-MIB |
| 1.3.6.1.4.1.476 | emerson | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1 | liebertCorp | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42 | liebertGlobalProducts | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3 | lgpFoundation | LIEBERT-GP-REGISTRATION-MIB |
| 1.3.6.1.4.1.476.1.42.3.5 | lgpPower | LIEBERT-GP-REGISTRATION-MIB |
| Numeric OID | Name | Module |
|---|---|---|
| 1.3.6.1.4.1.476.1.42.3.5.3 | lgpPwrStatus | LIEBERT-GP-POWER-MIB |
| 1.3.6.1.4.1.476.1.42.3.5.3.30 | lgpPwrInverterOverloadShutdownTime | LIEBERT-GP-POWER-MIB |