LIEBERT-GP-POWER-MIB :: lgpPwrBatteryTimeRemaining

MIB Reference — IPNetwork Monitor · Updated October 06, 2026

All MIBs › LIEBERT-GP-POWER-MIB › lgpPwrBatteryTimeRemaining

lgpPwrBatteryTimeRemaining

Module: LIEBERT-GP-POWER-MIB

OID (symbolic): LIEBERT-GP-POWER-MIB::lgpPwrBatteryTimeRemaining

OID (numeric): 1.3.6.1.4.1.476.1.42.3.5.1.18

Node type: OBJECT-TYPE

Type: Integer32

Access: read-only

Description: An estimate of the time to battery charge depletion under the present load conditions if the utility power is off and remains off, or if it were to be lost and remain off.

NOTE: A UPS is expected to provide a battery time remaining value when not operating on battery. However, if the system is not capable of providing this information, then this point will return 65535 to indicate that the value is unavailable.

What is lgpPwrBatteryTimeRemaining?

An estimate, in minutes, of how long the batteries can support the present load if utility power is or remains lost. Per the MIB's own note, a value of 65535 means the device can't calculate this and the reading should be ignored.

Examples

Walk all instances (SNMPv2c):

snmpwalk -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.1.18
snmpwalk -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrBatteryTimeRemaining

Get a specific instance (index 1):

snmpget -v2c -c public <target> 1.3.6.1.4.1.476.1.42.3.5.1.18.1
snmpget -v2c -c public <target> LIEBERT-GP-POWER-MIB::lgpPwrBatteryTimeRemaining.1

Start monitoring Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) with a free 30-day trial of IPNetwork Monitor. Create custom SNMP monitor using the LIEBERT-GP-POWER-MIB::lgpPwrBatteryTimeRemaining OID value, configure state conditions and alerts, and monitor any Liebert/Vertiv UPS/PDU and power-conditioning equipment (battery health) from a single console.

OID Breakdown

Upper-level ancestors (11 from the standard OID tree / other modules)
Numeric OIDNameModule
1isoLANART-AGENT
1.3orgAirPair-MIB
1.3.6dodAirPair-MIB
1.3.6.1internetAirPair-MIB
1.3.6.1.4privateAirPair-MIB
1.3.6.1.4.1enterprisesAirPair-MIB
1.3.6.1.4.1.476emersonLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1liebertCorpLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42liebertGlobalProductsLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3lgpFoundationLIEBERT-GP-REGISTRATION-MIB
1.3.6.1.4.1.476.1.42.3.5lgpPowerLIEBERT-GP-REGISTRATION-MIB
Numeric OIDNameModule
1.3.6.1.4.1.476.1.42.3.5.1lgpPwrBatteryLIEBERT-GP-POWER-MIB
1.3.6.1.4.1.476.1.42.3.5.1.18lgpPwrBatteryTimeRemainingLIEBERT-GP-POWER-MIB